Plan Review Notes For Permit 03051273 |
Permit Number |
03051273 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-05-16 00:00:00 | PROVIDE THE FOLLOWING INFORMATION FOR | | REVIEW: | | | | 1.OUTSIDE AIR CALCS AS PER 2001 FBC(M) | | TABLE 403.3. | | | | 2.SUBMITTAL ON THE CONDENSER UNIT | | STANDS LOCATED ON THE ROOF.SHOW | | COMPLIANCE WITH 2001 FBC 1511.7. | | | | 3.PLEASE INDICATE HOW CONDENSERS ARE | | TO BE ACCESSED.AS PER 2001 FBC(M) | | EQUIPMENT LOCATED ON THE ROOF AT A | | HEIGHT EXCEEDING 16 FT, REQUIRES AN | | PERMANENT MEANS OF ACCESS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|