Plan Review Notes
Plan Review Notes For Permit 03051273
Permit Number 03051273
Review Stop M
Sequence Number 1
Notes
Date Text
2003-05-16 00:00:00PROVIDE THE FOLLOWING INFORMATION FOR
 REVIEW:
  
 1.OUTSIDE AIR CALCS AS PER 2001 FBC(M)
 TABLE 403.3.
  
 2.SUBMITTAL ON THE CONDENSER UNIT
 STANDS LOCATED ON THE ROOF.SHOW
 COMPLIANCE WITH 2001 FBC 1511.7.
  
 3.PLEASE INDICATE HOW CONDENSERS ARE
 TO BE ACCESSED.AS PER 2001 FBC(M)
 EQUIPMENT LOCATED ON THE ROOF AT A
 HEIGHT EXCEEDING 16 FT, REQUIRES AN
 PERMANENT MEANS OF ACCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.