2003-06-30 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6716 |
| E-MAIL: [email protected] |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| |
| FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| ARE NUMBERED AS PER THE BUILDING PLAN |
| REVIEW OF 6/20/03: |
| |
| 2) THIS COMMENT HAS NOT BEEN PROPERLY |
| ADDRESSED.THE SUBMITTED COPIES OF ARCH |
| ALUMINUM DOOR PRODUCT APPROVAL NOA# |
| 01.0910.09 ARE BETTER QUALITY BUT THERE |
| IS A BLANK STRIP ACROSS EACH OF THE |
| DRAWING SHEETS.THIS BLANK STRIP |
| RENDERS THE MIAMI-DADE PRODUCT CONTROL |
| STAMPS AND THE ANCHOR FASTENER SCHEDULE |
| (SHEET 4 OF 4) ILLEGIBLE. SUBMIT LEGIBLE |
| COPIES. |
| |
| 3) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| FBC 1606.1.7WIND LOAD.THE PLANS |
| SHALL STATE THE BASIC WIND SPEED, WIND |
| IMPORTANCE FACTOR, WIND EXPOSURE |
| CATEGORY, INTERNAL PRESSURE COEFFICIENT, |
| AND EXTERIOR COMPONENT AND CLADDING |
| DESIGN WIND PRESSURES SO THAT THEY CAN |
| BE COMPARED TO THE ALLOWABLE PRESSURES |
| ON THE PRODUCT APPROVAL. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |