2003-06-30 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 6/20/03:
  
 2) THIS COMMENT HAS NOT BEEN PROPERLY
 ADDRESSED.THE SUBMITTED COPIES OF ARCH
 ALUMINUM DOOR PRODUCT APPROVAL NOA#
 01.0910.09 ARE BETTER QUALITY BUT THERE
 IS A BLANK STRIP ACROSS EACH OF THE
 DRAWING SHEETS.THIS BLANK STRIP
 RENDERS THE MIAMI-DADE PRODUCT CONTROL
 STAMPS AND THE ANCHOR FASTENER SCHEDULE
 (SHEET 4 OF 4) ILLEGIBLE. SUBMIT LEGIBLE
 COPIES.
  
 3) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FBC 1606.1.7WIND LOAD.THE PLANS
 SHALL STATE THE BASIC WIND SPEED, WIND
 IMPORTANCE FACTOR, WIND EXPOSURE
 CATEGORY, INTERNAL PRESSURE COEFFICIENT,
 AND EXTERIOR COMPONENT AND CLADDING
 DESIGN WIND PRESSURES SO THAT THEY CAN
 BE COMPARED TO THE ALLOWABLE PRESSURES
 ON THE PRODUCT APPROVAL.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN