Plan Review Notes For Permit 03051220 |
Permit Number |
03051220 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-05-19 00:00:00 | ************* UNSAT *************** | | | | 1)NOTE: PLEASE CORRELATE RISER DIAGRAM | | AND PANELS/OCP/WIRE SIZE. | | PANELS SHOWS 125 MAIN W/ 158A LOAD. | | RISER SHOWS 200A, BUT ONLY HAS 1/0`S? | | PLEASE SIZE PER 310-15B6/310-16 | | | | 2)NOTE: PLEASE PROVIDE NOTE TO ATTACH TO | | FOOTER STEEL. 250-50 | | | | 3)NOTE: PLEASE CLARIFY WHERE NEW SERVICE | | IS GOING/SHOW ON PLAN. | | | | 4)NOTE: PLEASE CLARIFY WHAT/IF ANY NEW | | ELECTRCIAL. PERMIT APPLICATION MENTIONS | | PARTIAL REMOD? | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected]. |
|