Plan Review Notes
Plan Review Notes For Permit 03051220
Permit Number 03051220
Review Stop E
Sequence Number 1
Notes
Date Text
2003-05-19 00:00:00************* UNSAT ***************
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND PANELS/OCP/WIRE SIZE.
 PANELS SHOWS 125 MAIN W/ 158A LOAD.
 RISER SHOWS 200A, BUT ONLY HAS 1/0`S?
 PLEASE SIZE PER 310-15B6/310-16
  
 2)NOTE: PLEASE PROVIDE NOTE TO ATTACH TO
 FOOTER STEEL. 250-50
  
 3)NOTE: PLEASE CLARIFY WHERE NEW SERVICE
 IS GOING/SHOW ON PLAN.
  
 4)NOTE: PLEASE CLARIFY WHAT/IF ANY NEW
 ELECTRCIAL. PERMIT APPLICATION MENTIONS
 PARTIAL REMOD?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  