Plan Review Notes For Permit 03051220 |
Permit Number |
03051220 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-06-06 00:00:00 | *******CORRECTIONS******* | | | | SAMANTHA THYNG, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | 1.)SEPARATE PERMITS REQUIRED. | | | | 2.)SIGN THE OWNER/AGENT LINE OF THE | | ENERGY CALCS. | | | | 3.)ADDITIONAL FEES DUE, $3.22. | | | | 4.)PROVIDE A SURVEY FOR THIS PROPERTY. | | | | 5.)STUCCO REQUIRED TO BE 7/8, FBC | | 2504.2.2, ASTM C1063. | | | | 6.)FIRESTOP REQUIRED FBC705.3. | | | | 7.)SUBMIT PRODUCT APPROVALS FOR | | THE CYPRESS DOORS, ROOF COVERING, | | DOUBLE DOORS, IMPACT WINDOWS (ALL TYPES) | | AND WINDOW MULLIONS. | | | | 8.)SHOW SIZES AND TYPES OF WINDOWS | | BEING REPLACED.INDICATE BEDROOM | | WINDOWS AND SHOW COMPLIANCE WITH | | EMERGENCY EGRESS REQUIREMENTS FBC1005.4. | | THE WINDOWS MARKED "SH EGRESS WIN" | | SCALED IS 33" X 51".THIS SIZE DOES NOT | | MEET EGRESS REQUIREMENTS UNLESS IT IS | | A SPECIAL EGRESS WINDOW.BE SURE TO | | SUBMIT THE CORRECT PRODUCT APPROVAL IF | | THIS IS THE PRODUCT TO BE USED. |
|