Date Text
2003-05-21 00:00:00PASSED/PROVISO
  
 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 705.1.2 PENETRATIONS SHALL BE PRO-
 TECTED BY AN APPROVED PENETRATION FIRE-
 STOP SYSTEM AS TESTED IN ACCORDANCE WITH
 ASTM E 814, WITH A MINIMUM POSITIVE
 PRESSURE DIFFERENTIAL OF 0.01 INCH OF
 WATER COLUMN AND AN F RATING OF NOT LESS
 THAN REQUIRED RATING OF THE WALL
 PENETRATED.
  
 FIRE STOP INFORMATION REQUIRED AT TIME
 OF INSPECTION