Notes
Date Text
2003-05-22 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 1) THERAPY JETS SHOWN ON POOL LAYOUT AT
 SWIMOUTS ARE NOT SHOWN ON SPECIFICATION
 FOR POOL AND SPA OR ON THE PIPING
 SCHEMATIC. PLEASE CLAIRFY
 2) FBC-2001 424.2.14.4 CONNECTIONS, ALL
 WATER HEATING EQUIPMENT SHALL BE INSTAL-
 LED WITH FLANGES OR UNION CONNECTIONS
 ADJACENT TO THE HEATER. (ADD TO NOTES)
  