Plan Review Notes
Plan Review Notes For Permit 03050855
Permit Number 03050855
Review Stop E
Sequence Number 2
Notes
Date Text
2004-04-20 00:00:00************ UNSAT ********************
  
 1)NOTE: PLEASE SEE A NEW PANEL "C" IS
 BEING SHOWN COMING FORMMETERMAIN.
 PLEASE INDICATE OCP. RISER MENTIONS TWO
 150A MB'S ONLY?
  
 2)NOTE: PLEASE ALSO SEE PANEL SCHEDULES
 MENTIONS SERVICE TO BE PROVIDED FOR
 EACH PANEL TO BE 200A'S YET 150A BRKRS
 FEED EACH.? SERVICE IS ALSO SHOWN AS
 400A.
  
 3)NOTE: PANEL "C" SHOWS 30A OCP FOR #12
 AWG FOR POOL PUMP.
  
 RECEPT ON PENINSULAR REDLINED TO BE GFI.
 210.8A6
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.