Notes |
Date |
Text |
2003-08-11 00:00:00 | BUILDING PROVISO | | | | 1) SUBMIT A REVISED TRUSS ANCHOR | | SCHEDULE WITH VALUES THAT DO NOT HAVE | | A ONE-THIRD INCEASE ON THE STEEL | | CALCULATIONS PER FBC 1609.4. SEE THE | | 2003 USP CATALOG AND THE 2002 SIMPSON | | HIGH WIND-RESISTANT CONSTRUCTION | | CATALOG FOR THE PROPER VALUES. | | | | 2) THE TRUSS DRAWINGS AND LAYOUT FOR | | SINGLE FAMILY DWELLINGS ARE NOT REQUIRED | | TO BE SUBMITTED FOR PLAN REVIEW. THEY | | ARE REQUIRED TO BE GIVEN TO THE FIELD | | INSPECTOR AT THE ROOF FRAMING INSPECTION | | NOTE: THE DRAWINGS DO NOT HAVE THE | | ORIGINAL WET SIGNATURE OF THE TRUSS | | ENGINEER ON THEM AND THE DRAWINGS HAVE | | DIFFERENT MEAN ROOF HEIGHTS LISTED ON | | THEM. |
|