Plan Review Notes
Plan Review Notes For Permit 03050855
Permit Number 03050855
Review Stop B
Sequence Number 1
Notes
Date Text
2003-06-23 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 SUBMIT A SOIL BORING TEST REPORT.
  
 4) ONE HOUR FIRE RATED GLASS BLOCK IS
 REQUIRED ON ZERO LOT LINE. SUBMIT
 MANUFACTURER'S SPECIFICATIONS AND
 LISTING INFORMATION FOR FIRE RATED GLASS
 BLOCK.
  
 5) THE DOOR IN THE WALL ADJACENT TO THE
 UNCONDITIONED GARAGE IS REQUIRED TO BE
 SOLID CORE OR INSULATED PER FBC CHAPTER
 13. PLEASE INDICATE ON PLANS.
  
 6) DETAIL 2 ON A3.3B INCORRECTLY
 SPECIFIES 5/8" STUCCO ON THE WALL. ASTM
 C 926 REQUIRES STUCCO APPLIED VERTICALLY
 ON LATH OVER SOLID BASE IS REQUIRED TO
 BE 7/8" THICK. PLEASE CORRECT.
  
 7) SPECIFY THE SHEATHING TYPE, FASTENER
 TYPE AND SPACING, VAPOR BARRIER, ETC.
 FOR THE EXTERIOR WALL THAT IS FORMED BY
 THE ROOF TRUSSES AS INDICATED BY THE
 DETAILS ON S4.
  
 8) SUBMIT ENGINEERED DRAWINGS, SPECS.,
 ETC. FOR THE BUTT GLASS WINDOW AS
 REQUIRED BY FBC 2406.2.
  
 9) FBC 1609.4 NO LONGER ALLOWS THE ONE-
 THIRD STRESS INCREASE ON STEEL ALLOWABLE
 STRESS DESIGN VALUES. PLEASE REVISE THE
 TRUSS ANCHOR SCHEDULE TO VALUES THAT DO
 NOT INCLUDE A STRESS INCREASE ON THE
 STEEL CALCULATIONS. SEE THE 2003 USP
 CATALOG AND THE 2002 SIMPSON HIGH-WIND
 CATALOG. THEUSP TA & TAR WITH (5) 10D
 X 1-1/2" NAILS HAS AN UPLIFT VALUE OF
 1230#, THE SIMPSON HETAL 12 WITH (15)
 10D X 1- 1/2" NAILS IS 1365#, ETC.
  
 10) PLEASE CLARIFY THAT THE G2 ANCHOR
 REQUIRES (2) STRAPS ON EACH TRUSS OF THE
 TWO MEMBER GIRDER.
  
 11) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - MULLIONS (UNCLIPPED) EXPIRED
 - 16'X 8' GARAGE DOOR (DESIGN LOAD IS
 NOT ADEQUATE FOR THE -39.7 THAT IS
 REQUIRED)
 - OUTSWING DOOR WITH TWO SIDELITES
 - OUTSWING FRENCH DOOR
 - ARCHED TOP FIXED GLASS WINDOWS
 (DESIGNER WINDOWS)
  
 12) PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714