 PLEASE NOTE THE FOLLOWING COMMENTS,MAKE
 NECESSARY CORRECTIONS TO THE PLANS AND
 RESUBMIT FOR REVIEW.
  
 1} PLEASE NOTE THAT THE GROUNDING
 ELECTRODE CONDUCTOR MUST COMPLY WITH
 250-50 INCLUDING THE FOOTER STEEL.
  
 2} NOTE #17 INCORRECTLY REFERENCES THE
 1996 NEC.SHOULD REFERENCE THE 1999 NEC.
  
 3} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 4} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 5} PLEASE NOTE THAT ALL PLANS
 DRAWN BY AN ARCHITECT/ENGINEER CONTAIN-
 ING A TITLE BLOCK, MUST BE SIGNED,
 DATED AND SEALED BY THE ARCH/ENGINEER OF
 RECORD. PER FS/FAC 481.221 & 471.025
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  