2003-05-15 00:00:00 | | | BUILDING COMMENTS | | -------- -------- | | | | 1] | | RAMP REQUIRES 28' OF HORIZONTAL | | PROJECTION WITH A RISE OF 28" IN ORDER | | TO COMPLY WITH THE 1/12 PITCH | | REQUIREMENT. FBC 11-4.8.2. | | | | 2] | | FBC 11-4.8.3[EXCEPTION] REQUIRES MIN. | | 44" CLEAR WIDTH, PLAN CALLS FOR 36". | | | | 3] | | FBC 11-4.8.5[3] REQUIRES A CLEAR WIDTH | | SEPERATION OF 1.5" BETWEEN HANDRAIL AND | | THE WALL. | | | | 4] | | PROVIDE EDGE PROTECTION AS PER FBC | | 11-4.8.7 | | | | 5] | | LANDING AT BOTTOM OF RAMP SHALL BE | | LOCATED WITHIN THE PROPERTY BOUNDARIES. | | | | | | | | | | L.MARTINEZ | | 805-6710 |
|