Plan Review Notes For Permit 03050588
Permit Number 03050588
Review Stop B
Sequence Number 1
Notes
Date Text
2003-06-16 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-WINDOW 34SH FOR BEDROOMS DOESN'T
 PROVIDE THE 24" CLEAR HEIGHT REQUIRED
 BY SEC. 1005.4.4 FBC 2001. REVISE AS
 REQUIRED.
 2-REVISE TRUSS ANCHOR SCHEDULE AND ALL
 DETAILS THAT ARE AFFECTED BY SECTION
 1609.4.3 FBC 2001, WHICH DOESN'T
 ALLOW THE STRESS INCREASE TO BE USED.
 3-STORM PANELS INSTALLATION SCHEDULE:
 ANCHOR TO BE SPACED 12"O.C. MAXIMUM
 WHEN EDGE DISTANCE IS LESS THAN 2".
 SEE ENGINEERED DRAWINGS.