2003-06-13 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-UPDATE TRUSS ANCHOR SCHEDULE AND ALL
 DETAILS THAT ARE AFFECTED BY SECTION
 1609.4.3 FBC 2001, WHICH DOESN'T
 ALLOW THE INCREASE IN THE ALLOWABLE
 STRESS.
 2-STORM SHUTTERS: ANCHOR SPACING TO BE
 12"O.C. (NOT 12.5") IF EDGE DISTANCE
 IS 2". SEE ENGINEERED DRAWINGS.