Plan Review Notes
Plan Review Notes For Permit 03050558
Permit Number 03050558
Review Stop E
Sequence Number 1
Notes
Date Text
2003-05-08 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE A DETAILED DRAWING
 INDICATING THE LOCATION OF ALL DEVICES
 TO BE INSTALLED,INCLUDING LOW VOLTAGE
 IF TO BE DONE UNDER THIS PERMIT,BEFORE
 CALLING FOR ROUGH INSPECTION.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 3} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE PER 210-12.
  
 4} THE LOAD CALCULATION MUST SHOW THE
 DRYER LOAD PER 220-18.(5000 VA.)
  
 5} PLEASE INDICATE THE AMPERE RATING OF
 THE DISCONNECTS AND PANELS ON THE RISER
 DIAGRAM.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718