2003-05-19 00:00:00************* UNSAT ********************
  
 1)NOTE: PLEASE SUBMIT A COMPLETE RISER
 DIAGRAM, LOAD CALCS, PANEL SCHEDULE(S)
 ETC FOR SERVICE OF HOUSE. 215-5
  
 2)NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/ GFI
 PROTECTED. 210-8A6
  
 3)NOTE: PLEASE SEE MISSING SD ON FIRST
 LEVEL AT BOTTOM OF STAIRS. (VICINITY)
 NFPA-72 8-1.4.2
  
 PLEASE NOTE, DUE TO PLANS NOT BEING
 COMPLETE AT THIS TIME, THERE MAY BE
 OTHER COMMENTS TO FOLLOW.
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 4)NOTE: PLEASE SEE MISING RECEPT PER
 210-52E FRONT AND REAR.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]