2003-06-18 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: |
| 1-REVISE ENERGY CALCULATIONS: |
| A)HOW IS R-12.9 INSULATION ACHIEVED ON |
| THE EXTERIOR MASONRY WALL. SEE PLANS |
| BY ARCHITECT. |
| B)PROVIDE ORIGINAL SIGNATURES ON BOTTOM |
| OF FORM. SEC. 103.0 CHAPTER 13, FBC/01 |
| 2-PROVIDE SOIL TEST REPORT FOR LOT 21. |
| ONE SUBMITTED IS FOR LOT 4. |
| 3-PROVIDE SPECS FOR WWM SUPPORTS IN CONC |
| SLAB. SEE SEC. 1909.3 FBC 2001. |
| 4-SPECIFY GLASS BLOCK SAFETY GLASS BY |
| SHOWER AREA IF FACE THICKNESS IS LESS |
| THAN 0.25". SEE SEC. 2405.2 FBC 2001. |
| 5-RESUBMIT STORM PANELS INFORMATION: |
| A)DRAWINGS ARE NOT THE SAME AS APPROVED |
| ON THE SBCCI REPORT. |
| B)ENGINEER IS NOT THE SAME AS THE ONE |
| LISTED ON THE SBCCI REPORT. |
| C)INCORRECT MEAN ROOF HEIGHT. |
| D)CHECK THE DESIGN PRESSURES CALCULATED |
| BY THE ENGINEER OF RECORD AND REVISE |
| AS REQUIRED. |
| E)REVISE ANCHOR SPACING ON INSTALLATION |
| SCHEDULE ACCORDING TO EDGE DISTANCE, |
| PANEL SPAN, DESIGN PRESSURES, TYPE OF |
| CONNECTION & STRUCTURE TO BE ATTACHED |
| TO.SEE ENGINEERED DRAWINGS. |
| F)REVISE MAXIMUM AND MINIMUN PANEL SPAN. |
| SEE ENGINEERED DRAWINGS. |
| G)CLEARLY MARK ON ENGINEERED DRAWINGS |
| ANCHOR TYPE AND SPACING TO BE USED. |
| |
| 6-PROVIDE 2X STRUCTURAL BUCK DETAIL FOR |
| ENTRY DOORS AS REUIRED ON PRODUCT |
| APPROVAL. |
| 7-UPDATE TRUSS ANCHOR SCHEDULE AND ALL |
| DETAILS THAT ARE AFFECTED BY SECTION |
| 1609.4.3 FBC 2001, WHICH DOESN'T ALLOW |
| THE STRESS INCREASE TO BE USED. |
| 8-PROVIDE PRODUCT APPROVAL FOR: |
| A)GLASS BLOCK (INFORMATION SUBMITTED IS |
| PART OF MANUFACTURER'S SPECS, NOT THE |
| ACTUAL PRODUCT APPROVAL). |
| B)ENTRY DOORS CURRENT PRODUCT APPROVAL |
| WITH DADE COUNTY LOGO AT LEFT BOTTOM |
| OF FRONT PAGE AND WITH DRAWINGS WITH |
| THE UPDATED STAMP AND NUMBER ON IT. |