Plan Review Notes For Permit 03050335
Permit Number 03050335
Review Stop B
Sequence Number 1
Notes
Date Text
2003-06-16 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE BULDING SECTION THRU
 FRAMED WALLS AT SECOND FLOOR. SPECIFY
 ALL FASTENERS TOP AND BOTTOM.
 **NOTE: STUCCO TO BE 7/8" MIN. AS PER
 ASTM C-926.
 2-GLASS BLOCK AT BATH TUB AREA TO BE
 SAFETY GLASS IF FACE THICKNESS IS LESS
 THAN 0.25". SEC. 2405.2 FBC 2001.
 3-PROVIDE GENERAL SPECIFICATIONS FOR
 FIREBLOCKING AT ALL CONCEALED SPACES,
 NOT JUST THE UNDERSIDE OF STAIRS. SEE
 SEC. 2305 FBC 2001.
 4-REVISE ENERGY CALCULATIONS: A)OWNER
 INFORMATION IS NOT CORRECT.
 B)COMPLETE HOUSE ADDRESS. ETC.
  
 5-PRODUCT APPROVAL FOR ALUMINUM MULLIONS
 IS EXPIRED. RESUBMIT CURRENT ONE.
 6-PROVIDE SOIL TEST REPORT PRIOR TO
 CONTRUCTION.
 7-SPECIFY CONNECTOR FOR TRUSS ON DETAIL
 1/S2. SEC. 104.2.1.2 CITY AMENDMENTS
 8-CLARIFY EXTERIOR STUCCO SOOFIT SPECS.
 ON SHEET A-5. NOTES ARE NOT CLEAR AND
 SOME ARE REPETITIVE. REVISE AS REQ'D.
 SEE ASTM C-926 AND ASTM C-1063.
 9-THERE ARE SOME CONNECTORS MISSING. SEE
 COMMENTS ON PLANS. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 10-UPDATE ALL TRUSS ANCHOR AND DETAILS
 THAT ARE AFFECTED BY SEC. 1609.4.3
 FBC 2001, WHICH DOESN'T ALLOW THE
 ALLOWABLE STRESS INCREASE TO BE USED.