2003-06-16 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: |
| 1-PROVIDE COMPLETE BULDING SECTION THRU |
| FRAMED WALLS AT SECOND FLOOR. SPECIFY |
| ALL FASTENERS TOP AND BOTTOM. |
| **NOTE: STUCCO TO BE 7/8" MIN. AS PER |
| ASTM C-926. |
| 2-GLASS BLOCK AT BATH TUB AREA TO BE |
| SAFETY GLASS IF FACE THICKNESS IS LESS |
| THAN 0.25". SEC. 2405.2 FBC 2001. |
| 3-PROVIDE GENERAL SPECIFICATIONS FOR |
| FIREBLOCKING AT ALL CONCEALED SPACES, |
| NOT JUST THE UNDERSIDE OF STAIRS. SEE |
| SEC. 2305 FBC 2001. |
| 4-REVISE ENERGY CALCULATIONS: A)OWNER |
| INFORMATION IS NOT CORRECT. |
| B)COMPLETE HOUSE ADDRESS. ETC. |
| |
| 5-PRODUCT APPROVAL FOR ALUMINUM MULLIONS |
| IS EXPIRED. RESUBMIT CURRENT ONE. |
| 6-PROVIDE SOIL TEST REPORT PRIOR TO |
| CONTRUCTION. |
| 7-SPECIFY CONNECTOR FOR TRUSS ON DETAIL |
| 1/S2. SEC. 104.2.1.2 CITY AMENDMENTS |
| 8-CLARIFY EXTERIOR STUCCO SOOFIT SPECS. |
| ON SHEET A-5. NOTES ARE NOT CLEAR AND |
| SOME ARE REPETITIVE. REVISE AS REQ'D. |
| SEE ASTM C-926 AND ASTM C-1063. |
| 9-THERE ARE SOME CONNECTORS MISSING. SEE |
| COMMENTS ON PLANS. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| 10-UPDATE ALL TRUSS ANCHOR AND DETAILS |
| THAT ARE AFFECTED BY SEC. 1609.4.3 |
| FBC 2001, WHICH DOESN'T ALLOW THE |
| ALLOWABLE STRESS INCREASE TO BE USED. |