Plan Review Notes For Permit 03050309 |
Permit Number |
03050309 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-05-17 00:00:00 | ************ UNSAT *************** | | | | 1)NOTE: PLEASE CORRELATE RISER AND | | PANEL SCHEDULE "A". SHOWS 60A #6`S TO | | SUB -"B", RISER SHOWN AS 2/0`S. | | | | 2)NOTE: PLEASE SEE AWG FOR 200A PANEL | | "A" SHOWN AS #2. 310-15B6, 2/0`S | | | | 3)NOTE: PLEASE SEE THAT GROUNDING ELEC- | | -TRODE SYSTEM TO FIRST MEANS OF DISC | | 250-24, METER/MAIN COMBO. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. PLEASE REMOVE OLD/VOIDED SHEETS | | AND INSERT NEW SHEETS INTO TWO COMPLETE | | SETS FOR REVIEW AND STAMPING. | | IF THERE ARE ANY QUESTIONS,PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|