Notes
Date Text
2003-05-17 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE CORRELATE RISER AND
 PANEL SCHEDULE "A". SHOWS 60A #6`S TO
 SUB -"B", RISER SHOWN AS 2/0`S.
  
 2)NOTE: PLEASE SEE AWG FOR 200A PANEL
 "A" SHOWN AS #2. 310-15B6, 2/0`S
  
 3)NOTE: PLEASE SEE THAT GROUNDING ELEC-
 -TRODE SYSTEM TO FIRST MEANS OF DISC
 250-24, METER/MAIN COMBO.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE REMOVE OLD/VOIDED SHEETS
 AND INSERT NEW SHEETS INTO TWO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 IF THERE ARE ANY QUESTIONS,PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]