Plan Review Notes For Permit 03050293 |
Permit Number |
03050293 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-05-19 00:00:00 | ******** PROVISO / REVISION ********** | | | | 1) NOTE: PLEASE SHOW ALL OUTLETS SERVING | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | -ED PER 210-8-A-6. | | INCLUDES KITCHEN ISLANDS. | | | | 2) NOTE: PLEASE SHOW ALL OUTLET SPACING | | TO MEET 2`,6`,12` RULE PER 210-52. | | BR#4 | | | | 3)NOTE: PLEASE SEE MISSIND DRYER LOAD | | IN LOAD CALCULATIONS. MIN 5KW | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|