2003-06-16 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03060285
 ADD: 6611 TRAVELER RD
 CONT: INTELLI HOMES
 TEL: (561)242-8877
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) MISSING IMPACT FEE SHEET.
  
 3) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 NO SOILS REPORT PROVIDED, REPORT TO
 STATE THE MINIMUM BEARING VALUE.
  
 4) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORT:
 A) OVERHEAD GARAGE DOOR
  
 5)1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23.
  
 6)A-6 WINDOW BUCK SLID.GLASS DOOR DETAIL
 1707.4.4.2 TAPERED BUCKS:
 SHALL EXTEND BEYOND THE INTERIOR FACE
 OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS SUPPORTED.
  
 7) SHEET A-2 DETAIL "D", REVISE DETAIL
 TO INDICATE BUCKET WITH FLOOR TRUSSES
 INTERSECTING AT 45 DEGREES.
  
 8) SSHEET S-2 DETAIL #1, HAS FIRE CUT AT
 WRONG POSITION.
  
 9)SHEET A-5 STUCCO NOTE# 5,CHAP.2504.2.2
 SHALL COMPLY WITH ASTM C-1063.
 RIB LATH SPACED @ 4" O.C. (EVERY RIB)
  
 10) SHEET A-5 STUCCO NOTE#7 CHAP2504.2.2
 SHALL COMPLY WITH 7.10.1.1 ATTACH ALL
 METAL PLASTER BASES TO SUPPORTS AT NO
 MORE THAN 7 IN. ALONG SUPPORTS EXCEPT
 FOR 3/8" RIB LATH THAT SHALL BE ATTACHED
 AT EACH RIB (4").
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)659-8096 X 8412
 FAX: (561)659-8026