2003-06-16 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 03060285 |
| ADD: 6611 TRAVELER RD |
| CONT: INTELLI HOMES |
| TEL: (561)242-8877 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| ACTION: DENIED |
| |
| 1) PROVIDE NOC RECORDED WITH THE CLERK |
| OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| |
| 2) MISSING IMPACT FEE SHEET. |
| |
| 3) FL BLD CODE 1804.2.2 QUESTIONABLE |
| SOILS, WHERE THE BEARING CAPACITY IS |
| NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| NO SOILS REPORT PROVIDED, REPORT TO |
| STATE THE MINIMUM BEARING VALUE. |
| |
| 4) FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORT, SBCCI OR DADE COUNTY |
| REPORT ARE ACCEPTED. MISSING REPORT: |
| A) OVERHEAD GARAGE DOOR |
| |
| 5)1609.4.3 LOAD REDUCTION. |
| WHEN STRUCTURAL EFFECTS DUE TO TWO OR |
| MORE LOADS IN COMBINATION WITH DEAD LOAD |
| ARE INVESTIGATED IN LOAD COMBINATIONS OF |
| 1609.4.1 OR 1609.4.2, THE COMBINED |
| EFFECTS DUE TO THE TWO OR LOADS MULTI- |
| PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD |
| LOADS SHALL NOT BE LESS THAN THE EFFECTS |
| FROM THE LOAD COMBINATION OF THE DEAD |
| LOAD PLUS THE LOAD PRODUCING THE LARGEST |
| EFFECTS. INCREAS IN ALLOWABLE STRESS SPE |
| CIFIED IN THE MATERIALS SECTIONS OF THIS |
| CODE OR A REFRENCED STANDARD SHALL NOT |
| BE USED WITH THESE LOAD COMBINATIONS |
| EXCEPT THAT A DURATION OF LOAD INCREASE |
| SHALL BE PERMITTED IN ACCORDANCE WITH |
| CHAPTER 23. |
| |
| 6)A-6 WINDOW BUCK SLID.GLASS DOOR DETAIL |
| 1707.4.4.2 TAPERED BUCKS: |
| SHALL EXTEND BEYOND THE INTERIOR FACE |
| OF THE WINDOW OR DOOR FRAME SUCH THAT |
| FULL SUPPORT OF THE FRAME IS SUPPORTED. |
| |
| 7) SHEET A-2 DETAIL "D", REVISE DETAIL |
| TO INDICATE BUCKET WITH FLOOR TRUSSES |
| INTERSECTING AT 45 DEGREES. |
| |
| 8) SSHEET S-2 DETAIL #1, HAS FIRE CUT AT |
| WRONG POSITION. |
| |
| 9)SHEET A-5 STUCCO NOTE# 5,CHAP.2504.2.2 |
| SHALL COMPLY WITH ASTM C-1063. |
| RIB LATH SPACED @ 4" O.C. (EVERY RIB) |
| |
| 10) SHEET A-5 STUCCO NOTE#7 CHAP2504.2.2 |
| SHALL COMPLY WITH 7.10.1.1 ATTACH ALL |
| METAL PLASTER BASES TO SUPPORTS AT NO |
| MORE THAN 7 IN. ALONG SUPPORTS EXCEPT |
| FOR 3/8" RIB LATH THAT SHALL BE ATTACHED |
| AT EACH RIB (4"). |
| |
| LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS, OR ATTACHED |
| SEPARATELY. WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| THE PLANS WHEN RESUBMITTING PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN |
| BE FOUND, WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| JIM WITMER |
| BUILDING PLAN REVIEW |
| TEL: (561)659-8096 X 8412 |
| FAX: (561)659-8026 |