2005-09-19 00:00:00PROVISO:
 1.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO ALARM/STROBE IS
 REQUIRED PER 2001 FBC(M)606.2.1.
  
 2.NO COMBUSTIBLES ALLOWED ABOVE THE
 CEILING IN THE RETURN AIR PLENUM - 2001
 FBC(M)602.2.1.
  