2005-08-04 00:00:00********** UNSAT **********
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEWS AND SEE NEW NOTES DUE TO CHNAGES
 IN PLANS.
 **PLEASE SEE PLANS ARE FOR FINAL/ CO AND
 ALL ON PLANS MUST BE CORRECTED AT 100%.
  
 1)NOTE: PLEASE SEE NO "EQUIPMENT
 GROUNDING CONDUCTORS" ARE INSTALLED
 UNTIL AFTER THE FIRST MEANS OF
 DISCONNECT. PLEASE SEE 250.6,250.24, SEE
 RISER DIAGRAM.
  
 2)NOTE: PLEASE SEE SEC'S SHOWN FROM FPL
 TO GUTTER?? PLEASE SEE 2-SETS OF 3/0'S
 ARE ONLY RATED FOR 400AS' AND SERVICE
 SHOWS MIN LOADS AFTER ALL DERATINGS OVER
 400A'S.
 PLEASE SEE 240.4,310.16 FOR MIN SEC'S
 REQUIRED.
  
 3)NOTE: PLEASESEE 250.66 FOR ANY
 ADJUSTMENT IN GROUNDINGELECTRODE
 CONDUCTOR? PLEASE SEE ORIGINAL SET WAS
 REDLINED DUE TO INCORRECT SIZE SHOWN.
  
 4)NOTE: PLEASE SEE MISSING AIC RATING
 FOR MAIN DISCONNECT FEEDING PANEL "D".
 110.9, 215.5
  
 5)NOTE: PLEASE CORRELATE PANEL "C" WITH
 RISER DIAGRAM. PLEASESEE A MCB IS
 REQUIRED FOR GROUPING OF MAINS ETC.
 230.72,215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  