Plan Review Notes For Permit 03050246 |
Permit Number |
03050246 |
|
Review Stop |
E |
Sequence Number |
6 |
|
Notes |
Date |
Text |
2005-08-04 00:00:00 | ********** UNSAT ********** | | | | PLEASE SEE SOME NOTES FROM PREVIOUS | | REVIEWS AND SEE NEW NOTES DUE TO CHNAGES | | IN PLANS. | | **PLEASE SEE PLANS ARE FOR FINAL/ CO AND | | ALL ON PLANS MUST BE CORRECTED AT 100%. | | | | 1)NOTE: PLEASE SEE NO "EQUIPMENT | | GROUNDING CONDUCTORS" ARE INSTALLED | | UNTIL AFTER THE FIRST MEANS OF | | DISCONNECT. PLEASE SEE 250.6,250.24, SEE | | RISER DIAGRAM. | | | | 2)NOTE: PLEASE SEE SEC'S SHOWN FROM FPL | | TO GUTTER?? PLEASE SEE 2-SETS OF 3/0'S | | ARE ONLY RATED FOR 400AS' AND SERVICE | | SHOWS MIN LOADS AFTER ALL DERATINGS OVER | | 400A'S. | | PLEASE SEE 240.4,310.16 FOR MIN SEC'S | | REQUIRED. | | | | 3)NOTE: PLEASESEE 250.66 FOR ANY | | ADJUSTMENT IN GROUNDINGELECTRODE | | CONDUCTOR? PLEASE SEE ORIGINAL SET WAS | | REDLINED DUE TO INCORRECT SIZE SHOWN. | | | | 4)NOTE: PLEASE SEE MISSING AIC RATING | | FOR MAIN DISCONNECT FEEDING PANEL "D". | | 110.9, 215.5 | | | | 5)NOTE: PLEASE CORRELATE PANEL "C" WITH | | RISER DIAGRAM. PLEASESEE A MCB IS | | REQUIRED FOR GROUPING OF MAINS ETC. | | 230.72,215.5 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|