2004-02-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) FROM PREVIOUS REVIEWS.
 DISPLAY BATHROOM SHOWER DETAILS NOT
 SUBMITTED. SECTION 11-4.21 AND ALL SUB-
 SECTIONS. (COMMENT #2 FROM PREVIOUS RE-
 VIEWS).
 2) FROM PREVIOUS REVIEWS.
 SUBMIT DETAIL FOR GRAB BARS FOR W/C,
 SHOW LAV HEIGHT AND CLEAR FLOOR SPACE
 FOR LAV AND WATER CLOSET.
 3) FROM PREVIOUS REVIEWS.
 SUBMIT CALCULATIONS FOR ROOF GUTTERS AND
 DOWNSPOUTS. SHOW TOTAL SQUARE FOOTAGE
 FOR EACH ROOF AREA. AREA OF UPPER ROOF
 THAT DRAINS TO LOWER ROOF SHALL BE ADDED
 WHEN SIZING GUTTERS AND DOWN SPOUTS.
 SHOW IN CALCULATIONS. ALSO SHOW 1/2 AREA
 OF ALL VERTICAL WALLS INCLUDING PARAPETS
 ADDED TO CALCULATIONS. TABLE 1106.2 AND
 TABLE 1106.6. INDICATE PITCH (SLOPE) OF
 GUTTER AND SHOW WHERE THE PITCH TO EACH
 DOWNSPOUT STARTS. (HIGH POINT)
 4) NEW COMMENT. BAR SINK SHALL COMPLY
 WITH 11-4.24 AND ALL SUBSECTIONS. PROVI-
 DE A DETAIL SHOWING HEIGHT, CLEAR FLOOR
 SPACE, KNEE CLEARANCE, DEPTH, EXPOSED
 PIPES, FAUCETS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]