Review Stop FIRE
Sequence Number 4
Notes
Date Text
2003-12-24 00:00:001) THE FIRE DEPARTMENT CONNECTION SHALL
 BE PROVIDED WITH 7'- 6" CLEARANCE.
  
 2) THE FIRE DEPARTMENT CONNECTION SHALL
 BE WITHIN 150 FEET OF A FIRE HYDRANT.
  
 3) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER SYSTEM REMODEL. THE
 FIRE SPRINKLER SYSTEM AND ANY FIRE
 ALARM SYSTEM EQUIPMENT MUST BE UL
 LISTED FOR CENTRAL STATION SERVICE SINCE
 THIS BECAME EFFECTIVE AUGUST 1, 2003.
  
 4) THE DESIGN TEAM AND OWNER RED-LINED
 THE DRAWINGS ON 12-24-03 AND MADE
 CORRECTIONS TO THE DRAWINGS.
  
 5) THE BACKFLOW DEVICE FOR THE FIRE
 SPRINKLER SYSTEM IS REQUIRED TO HAVE
 TAMPER SWITCHES AND A CHAIN AND LOCK.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 BUREAU OF FIRE PREVENTION