2003-11-05 00:00:00 | ************** UNSAT *********** |
| |
| PLEASE NOTE: OWES RESUB FEE, DID NOT |
| GET ACCESSED WHEN RESUBMITTED. |
| |
| PLEASE NOTE: PER FS 713, IF WORK HAS |
| NOT COMMENCED W/IN 90 DAYS OF RECORDING |
| NOC, A NEW RECORDED NOC IS REQ'D BEFORE |
| PICKING UP PERMIT. |
| |
| 1)NOTE: PLEASE SEE RISER DIAGRAM WHICH |
| HAS NOW BEEN REVISED TO ADDRESS PREVIOUS |
| COMMENTS. |
| RISER NOW SHOWS EQUIPMENT GROUNDING |
| CONDUCTORS BEFORE THE FIRST MEANS OF |
| DISCONNECT WHICH IS NOW PARALLELING THE |
| NEUTRAL? PLEASE SEE ORIG COMMENT, ASK |
| FOR MISSING EQUIPMENT GROUNDING FROM |
| MAIN DISC'S TO PANELS.250.110,250.122. |
| PER 250.24 |
| |
| 2)NOTE: PLEASE SEE RISER, NOW SHOWS A |
| #3 ALONG WITH THE 4 500MCM CONDUCTORS |
| FROM GUTTER TO METER AND THEN TO GUTTER |
| ON LOAD SIDE OF K-7? PLEASE CLARIFY |
| WHAT THIS #3 CONDUCTOR IS??? |
| PLEASE ALSO SEE 250.24 |
| |
| 3)NOTE: PLEASE SEE PLANS AND SHOW |
| LOCATION OF SIGN CIRCUIT. IT IS NOTED |
| THAT PANEL SCHEDULE SHOWS CIRCUIT |
| HOWEVER THIS COULD NOT BE LOCATED ON |
| PLANS. |
| |
| 4)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| PLANS. PLEASE ALSO SEE 700.12E |
| PLEASE SEE ONE SET OF PLANS HAS A FEW |
| OF THESE ITEMS HIGHLIGHTED. |
| |
| 5)NOTE: PLEASE CORRELATE SYMBOLS ON |
| PLANS AND SYMBOL LIST. |
| |
| SOME OF THE ABOVE NOTES ARE FROM FIRST |
| TWO REVIEW. A NOTICE WAS GIVEN ON PREVI- |
| -OUS REVIEW IN REF TO FS 553.80(2)(B) |
| PLEASE SEE AS PER FS A 4X FEE MUST NOW |
| BE ASSESSED AND MUST BE PAID BEFORE |
| RESUBMITTING FOR NEXT REVIEW. |
| PLEASE SEE BZ ATTACHED $11,924.42, THIS |
| FEE MAY BE ADJUSTED DUE TO VALUATION |
| ADJUSTMENT ON PERMIT FEE. |
| NEW COMMENT: |
| 1)NOTE: PLEASE KNOW THAT PER FS 471.025 |
| AND FAC 61G15-23.002, A NOTICE FROM THE |
| FBPE'S HAS BEEN GIVEN TO THIS OFFICE |
| AND REQUIRE'S ENGINEER TO SIGN PLANS |
| WITH A SIGNATURE AND INITIALS ARE NOT |
| ACCEPTABLE. MUST SIGN A MIN OF FIRST |
| AND LAST NAME AS RECORDED ON SAID SEAL. |
| |
| PLEASE TAKE ALL OLD /VOIDED SHEETS OUT |
| AND INSERT NEW SHEETS INTO COMPLETE |
| SETS FOR REVIEW AND STAMPING. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW.IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |