2003-12-18 00:00:00*****CORRECTIONS******
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE HANDRAIL DETAIL ON SHEET A1.1
 IS TO COMPLY WITH 1608.2.1.
  
 2.)INCLUDE A TITLE BLOCK ON SHEETS
 FS1,FS2,FS3 AND SEAL THE CONCRETE FLOOR
 SYSTEM SHEETS, FS61G15-23.002.
  
 3.)SEE THE PREVIOUS LIST, HOW WILL
 THE #4@12" OC TERMINATE IN THE B1 BEAM
 FOR THE BALCONY SHOWN ON SHEET S1.1?
 NOT ADDRESSED.
  
 4.)SEE THE PREVIOUS LIST IN REGARDS
 TO THE BALUSTRADE DETAIL.EMBEDMENT AT
 THE TOP WAS GIVEN BUT NOT EMBEDMENT AT
 THE BOTTOM.SEE 1608.2.2 FOR MINIMUM
 DESIGN LOADING AND PROVIDE SUPPORTING
 CALUCLATIONS TO DEMONSTRATE COMPLIANCE
 WITH SAME.SEE ALSO FBC1015 FOR MINIMUM
 GUARDRAIL DIMENSIONS AND NOTE SAME IN
 THE DESIGN CRITERIA.
  
 5.)THE ENERGY CALC TOTAL SQUARE
 FOOTAGE DOES NOT APPEAR TO BE THE SAME
 AS THE A/C AREA ON THE PLAN.ADDRESS.
  
 6.)WHEN MAKING CHANGES, IN ORDER TO
 EXPEDITE PLAN REVIEW, CLEARLY CLOUD AND
 NUMBER ALL REVISIONS.SUBMIT OLD SHEETS
 (APPROVED ZONING AND IMPACT FEE STAMP
 ARE NOT ON THIS SET AND ARE REQUIRED
 BEFORE THE PERMIT CAN BE ISSUED).
  
 7.)SUBMIT THE FOLLOWING PRODUCT
 APPROVALS:
 MULLIONS
 FIXED GLASS
 GLASS BLOCK
  
 8.)NOTICE OF COMMENCEMENT IS EXPIRED
 (90 DAYS WITHOUT COMMENCING WORK),
 FS713.13.