2003-09-29 00:00:00************* UNSAT *******************
  
 PLEASE SEE THAT SOME NOTES FROM FIRST
 REVIEW NEED TO BE ADDRESSED.
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL SCHEDULES
 SUBMITTED.
 IE, ACCU-1 ON ROOF SHOWN ON GFI RECEPT
 CIRCUIT. PLEASE GO THROUGH OTHERS.
  
 2)NOTE: PLEASE SEE 700.12E FOR CIRCUIT-
 -ING OF EM/EXT LTS.
 PLEASE ALSO SEE 700.16 STAIRWAY?
  
 3)NOTE: PLEASE SEE SERVICE LOCATION
 OUTSIDE, APPEARS TO ONLY SHOW ONE METER
 AND THREE PANELS/ORDISCS.
  
 4)NOTE: PLEASE SEE /CLARIFY MEANS OF
 EEQUIPMENT GROUNDING FROM MAIN DISC'S TO
 PANELS. 250.24/250.110/250.122
  
 5)NOTE: PLEASE CLARIFY LOCATION OF REQ'D
 SIGN CIRCUIT 600.5
  
 6)NOTE: PLEASE SEE FIRE PLAN REVIEW
 NOTES THAT WILL HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 7)NOTE: CIRCUIT FOR OUTSIDE WALLPACKS
 IS NOW SHOWN ,HOWEVER HOW ARE THESE
 CONTROLLED? PC/TC? ARE THEY ON 24/7?
  
 8)NOTE: PLEASE CLARIFY WHAT APPEARS TO
 BE A FAN OUTSIDE NEXT TO SERVICE?
  
 9)NOTE: PLEASE CORRELATE SYMBOLS FOR
 EXIT LTS AND ANY OTHERS.
 PLEASE CLARIFY MEANS OF LIGHTING STAIR-
 WAY. LS 101 5-8
  
 10)NOTE: PLEASE SEE ATTACHED COPY OF
 FS 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONALS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 PLEASE NOTE, MAX FUTURE TENANT TO BE
 100A'S.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW