2003-09-29 00:00:00 | ************* UNSAT ******************* |
| |
| PLEASE SEE THAT SOME NOTES FROM FIRST |
| REVIEW NEED TO BE ADDRESSED. |
| |
| 1)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| PLANS AND CORRELATE WITH PANEL SCHEDULES |
| SUBMITTED. |
| IE, ACCU-1 ON ROOF SHOWN ON GFI RECEPT |
| CIRCUIT. PLEASE GO THROUGH OTHERS. |
| |
| 2)NOTE: PLEASE SEE 700.12E FOR CIRCUIT- |
| -ING OF EM/EXT LTS. |
| PLEASE ALSO SEE 700.16 STAIRWAY? |
| |
| 3)NOTE: PLEASE SEE SERVICE LOCATION |
| OUTSIDE, APPEARS TO ONLY SHOW ONE METER |
| AND THREE PANELS/ORDISCS. |
| |
| 4)NOTE: PLEASE SEE /CLARIFY MEANS OF |
| EEQUIPMENT GROUNDING FROM MAIN DISC'S TO |
| PANELS. 250.24/250.110/250.122 |
| |
| 5)NOTE: PLEASE CLARIFY LOCATION OF REQ'D |
| SIGN CIRCUIT 600.5 |
| |
| 6)NOTE: PLEASE SEE FIRE PLAN REVIEW |
| NOTES THAT WILL HAVE AN AFFECT ON |
| ELECTRICAL PLANS. |
| |
| 7)NOTE: CIRCUIT FOR OUTSIDE WALLPACKS |
| IS NOW SHOWN ,HOWEVER HOW ARE THESE |
| CONTROLLED? PC/TC? ARE THEY ON 24/7? |
| |
| 8)NOTE: PLEASE CLARIFY WHAT APPEARS TO |
| BE A FAN OUTSIDE NEXT TO SERVICE? |
| |
| 9)NOTE: PLEASE CORRELATE SYMBOLS FOR |
| EXIT LTS AND ANY OTHERS. |
| PLEASE CLARIFY MEANS OF LIGHTING STAIR- |
| WAY. LS 101 5-8 |
| |
| 10)NOTE: PLEASE SEE ATTACHED COPY OF |
| FS 553.80(2)(B) WITH RESPECT TO DESIGN |
| PROFESSIONALS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| PLEASE NOTE, MAX FUTURE TENANT TO BE |
| 100A'S. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |