2003-09-30 00:00:00SHEET A1.0 NOW DECLARES UL DESIGN U 906
 FOR THE FIRE RATED STAIRS.U 906
 INVOKES 6" PROPRIETARY BLOCK FOR THE
 DESIGN.
 THE PLANS INDICATE 8" BLOCK FOR THE
 STRUCTURAL.PLEASE REVISE AS NECESSARY.
  
 SHEET A1.0 CALLS FOR HANDRAILS TO BE
 DESIGNED FOR 50 PLF IN ANY DIRECTION.
 THIS DOES NOT COMPLY WITH FBC 1608.2.1.
  
 THE 90# LIVE LOAD SHOWN FOR THE STORAGE
 AREA ON SHEET A2.0 IS LESS THAN THE
 MINIMUM 125# LIVE LOAD FOR LIGHT
 STORAGE IN FBC TABLE 1604.1.
 PLEASE REVISE AS NECESSARY.
  
 SHEET A1.1 MAKES NOTE OF FIRE
 SPRINKLERSIF THE BUILDING IS TO HAVE
 FIRE
 SPRINKLERS, THE DESIGN IS REQUIRED TO
 BE ON THE PERMIT PLANS.SEE FBC
 104.3.1.1 #4.
  
 AS PREVIOUSLY NOTED, SEE FBC 104.2.1.1
 FOR THE ROOF COVERING DESIGN
 INFORMATION NECESSARY ON THE PLANS.
  
 THE PREVIOUS CHECK LIST REQUESTED THE
 DESIGN INFORMATION FOR THE PRE-CAST
 CONCRETE FLOOR SYSTEM.SEE CHAPTER
 61G15-30 RESPONSIBILITY RULES COMMON TO
 ALL ENGINEERS, OF THE FL ADMINISTRATIVE
 CODE AS PERTAINS TO DELEGATING
 ENGINEERING REQUIREMENTS.
  
 HOW WILL THE #4@12" OC TERMINATE IN
 THE B1 BEAM FOR THE BALCONY SHOWN ON
 SHEET S1.1?
  
 THE BALUSTRADE CONNECTION DETAIL ON
 SHEET A1.1 IS SOMEWHAT VAGUE WITH ITS
 >>1/2" DOWEL TOP AND BOTTOM <<.WHAT
 ISTHE EMBEDMENT DEPTH OF THE DOWEL(S)?
 WILL THEY BE CAST IN PLACE?SEE FBC
 1608.2.2 FOR MINIMUM DESIGN LOADING AND
 PROVIDE SUPPORTING CALCULATIONS TO
 DEMONSTRATE COMPLIANCE WITH SAME.
 SEE ALSO, FBC 1015 FOR MINIMUM GUARD
 RAIL DIMENSIONS AND NOTE SAME IN THE
 DESIGN CRITERIA.