Plan Review Notes
Plan Review Notes For Permit 03050246
Permit Number 03050246
Review Stop P
Sequence Number 1
Notes
Date Text
2003-06-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) PLEASE SUBMIT CALCULATIONS FOR MINI-
 MUM FACILITIES. TABLE 403.1 - INDICATE
 TOTAL AREA FOR EACH OCCUPANCY AND TOTAL
 FIXTURES REQUIRED FOR EACH OCCUPANCE.
 (ALSO SEE TABLE 1003.1 BLDG CODE)
 2) IF BATHING ROOMS ARE PROVIDED, THEN
 EACH PUBLIC AND COMMON USE TOILET ROOM
 SHALL COMPLY WITH 11-4.23
 3) SHT A1.0 LOUNGE AND KITCHEN SINKS
 SHALL COMPLY WITH 11-4.24 AND ALL SUB-
 SECTIONS. PLEASE PROVIDE DETAILS.
 4) SHT A1.0 ALL TOILET ROOMS SHALL SHOW
 LENGTH AND WIDTH ON PLANS. ALL TOILET
 ROOMS SHALL COMPLY WITH 11-4.22 AND ALL
 SUBSECTIONS. PLEASE PROVIDE DETAILS.
 5) SHT A1.1 - SEE COMMENT #4.
 6) SHT A1.2 SUBMIT CALCULATIONS FOR ROOF
 GUTTER AND DOWNSPOUTS. SHOW SQUARE FOOT-
 AGE FOR EACH ROOF AREA. AREA OF UPPER
 ROOF THAT DRAINS TO LOWER ROOF SHALL BE
 ADDED WHEN SIZING GUTTERS AND DOWNSPOUTS
 OF LOWER ROOF. BE SURE TO SHOW THIS IN
 THE CALCULATIONS. TABLE 106.2 & TABLE
 1106.6. INDICATE PITCH OF GUTTER, AND
 SHOW WHERE THE PITCH TO EACH DOWNSPOUT
 STARTS.
 7) DOWNSPOUTS SHALL TERMINATE A MINIMUM
 OF 1' FROM BLDG WALL. SEC 1503.4.4
 8) SHT A1.2 SHOWS ROOF DRAIN ON RIGHT
 SIDE OF LOWER ROOF. IT STATES SEE MECH.
 DRAWINGS. UNABLE TO LOCATE ON MECH.
 DRAWINGS. PLEASE CLAIRFY.
 9) SHT MEP2.4 PLUMBING NOTES #16, SEPAR-
 ATE PERMIT/PLANS REQD. FOR GAS. 104.1.1
 10) SHT MEP3.0 WATER HEATER IN LOUNGE TO
 BE ACCESSIBLE. SEC 501.4 - SUBMIT DETAIL
 11) SHT MEP3.0 SANT RISER DIAGRAM, ONLY
 FIXTURES FROM THE BATHROOM GROUP SHALL
 DRAIN THROUGH THE HORIZONTAL WET VENT.
 SEC 909.1 - 1ST FLOOR KIT. SINK, SECOND
 FLOOR LOUNGE, & SECOND FLOOR BATHROOM
 SHALL ALL TIE IN DOWNSTREAM OF WET VENT.
 12) SHT MEP3.0 WATER RISER DIAGRAM, 1ST
 FLOOR W/C AND LAV NOT SHOWN ON RISER.
 HOSE BIBB IN ELECTRIC ROOM? PLEASE
 CLAIRFY. IF H.B. IS FOR GROUND A HARD
 CAP IS SUGGESTED. NO SUPPLY TO H.B. IS
 SHOWN ON RISER DIAGRAM.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved