2003-05-19 00:00:00DENIED:MECHANICAL PERMIT 03050253
  
 1.PLEASE PROVIDE OUTSIDE AIR CALCS
 AS PER 2001 FBC(M) TABLE 403.3.
  
 2.PROVIDE CALCULATIONS FOR AIR CHANGES
 IN GARAGE AREA AS PER TABLE 403.3.
  
 3.PLAN SHEET MEP3.0 INDICATES EF-1
 TO RUN 15 MINUTES PER HOUR.AS PER 2001
 FBC(M) 403.4 MECHANICAL VENTILATION NOT
 REQUIRED TO RUN CONTINUOUSLY WHERE THE
 SYSTEM IS ARRANGED TO OPERATE AUTO-
 MATICALLY UPON DETECTION OF A CONCENTRA-
 TIONOF CARBON MONOXIDE OF 25 (PPM) BY
 APPROVED AUTOMATIC DETECTION DEVICES.
  
 4.CONDENSER UNIT STANDS ON ROOF SHALL
 COMPLY WITH 2001 FBC 1511.7 FOR THE
 DISTANCE BETWEEN THE ROOF FINISHED
 SURFACE AND THE BOTTOM OF THE SUPPORT
 RAIL.
  
 5.FIRE DAMPERS ARE NOT INDICATED ON
 PLAN.PLEASE NOTE, FIRE DAMPERS ARE
 REQUIRED WHERE DUCTS PENETRATE A FIRE
 RATED WALL PARTITION OR FLOOR.PLEASE
 SHOW LOCATIONS OF ALL FIRE DAMPERS THAT
 ARE REQUIRED.2001 FBC(M) 607.6
  