2003-05-19 00:00:00 | DENIED:MECHANICAL PERMIT 03050253 |
| |
| 1.PLEASE PROVIDE OUTSIDE AIR CALCS |
| AS PER 2001 FBC(M) TABLE 403.3. |
| |
| 2.PROVIDE CALCULATIONS FOR AIR CHANGES |
| IN GARAGE AREA AS PER TABLE 403.3. |
| |
| 3.PLAN SHEET MEP3.0 INDICATES EF-1 |
| TO RUN 15 MINUTES PER HOUR.AS PER 2001 |
| FBC(M) 403.4 MECHANICAL VENTILATION NOT |
| REQUIRED TO RUN CONTINUOUSLY WHERE THE |
| SYSTEM IS ARRANGED TO OPERATE AUTO- |
| MATICALLY UPON DETECTION OF A CONCENTRA- |
| TIONOF CARBON MONOXIDE OF 25 (PPM) BY |
| APPROVED AUTOMATIC DETECTION DEVICES. |
| |
| 4.CONDENSER UNIT STANDS ON ROOF SHALL |
| COMPLY WITH 2001 FBC 1511.7 FOR THE |
| DISTANCE BETWEEN THE ROOF FINISHED |
| SURFACE AND THE BOTTOM OF THE SUPPORT |
| RAIL. |
| |
| 5.FIRE DAMPERS ARE NOT INDICATED ON |
| PLAN.PLEASE NOTE, FIRE DAMPERS ARE |
| REQUIRED WHERE DUCTS PENETRATE A FIRE |
| RATED WALL PARTITION OR FLOOR.PLEASE |
| SHOW LOCATIONS OF ALL FIRE DAMPERS THAT |
| ARE REQUIRED.2001 FBC(M) 607.6 |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE |