Plan Review Notes For Permit 03050246 |
Permit Number |
03050246 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-06-05 00:00:00 | 1) DOOR SCHEDULE INDICATES NO RATED | | FIRE DOORS. PLEASE EXPLAIN RATIONALE. | | | | 2) DOORS 19 AND 20 OPPOSE ONE ANOTHER. | | | | 3) A KNOX-BOX WILL BE REQUIRED FOR THE | | BUILDING. | | | | 4) IN SOME OTHER LOCALES DOORS OPPOSE | | ONE ANOTHER. | | | | 5) PLEASE CLEARLY ILLUSTRATE ALL | | EMERGENCY LIGHTS. | | | | 6) PLEASE SHOW HANDRAILS ON BOTH SIDES | | OF ALL STAIRS. | | | | 7) PLEASE SHOW PRESCRIPTIVE STRENGTH | | REQUIREMENTS FOR HANDRAILS. | | | | 8) NO FIRE SPRINKLER PLANS PROVIDED WITH | | PLANS. DRAWINGS ILLUSTRATE A FIRE LINE | | ENTERING THE BUILDING. PLEASE PROVIDE | | REQUIRED INFORMATION. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8097,EXT.8497 | | 835-2910 |
|