Plan Review Notes
Plan Review Notes For Permit 03050246
Permit Number 03050246
Review Stop E
Sequence Number 1
Notes
Date Text
2003-05-13 00:00:00************* UNSAT ******************
  
 1)NOTE: PLEASE INCLUDE LICENSE # IN
 TITLE BLOCK FOR ARCH OF RECORD AS REQ`D
 IN FS/ FAC 61G1-16.004/ 481
  
 2)NOTE: PLEASE PROVIDE ROOM DESIGNATION
 ON ALL SHEETS. PERMIT APPLICATION
 MENTIONS A SHOWROOM?
  
 3)NOTE: PLEASE CLARIFY HEIGHTS OF GFI`S
 IN GARAGE.
  
 4)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE W/ SUBMITTE PANEL
 SCHEDULES. PLEASE CIRCUIT ALL EM/ EXT LT
 -S PER 700-16E
  
  
 5)NOTE: PLEASE SHOW CONTROL AND CIRCUIT-
 ING OF OUTSIDE LIGHTING.
  
 6)NOTE: PLEASE SEE PLANS, THERE SEEMS
 TO BE CIRCUITING SHOWN IN AREAS THAT DO
 NOT GO TO ANYTHING?
  
 7)NOTE: PLEASE COMPLETE LOAD CALCULATION
 -S. SHOWN BLANK?
  
 8)NOTE: PLEASE SHOW MISSING EQUIPMENT
 GROUNDING CONDUCTORS FROM MAIN DISC`S TO
 PANELS. 250-110/250-122
  
 9)NOTE: PLEASE CLARIFY SIZE ALLOWED FOR
 FUTURE TENANT/METER AND MAIN DISC?
 PLEASE BE SURE TO SIZE SEC`S FOR FUTURE
 LOADS ALSO. SERVICE IS 400A`S AT PRESENT
 TIME.
  
 10)NOTE: PLEASE SIZE GROUNDING ELECTRODE
 CONDUCTOR PER 250-66. BASED ON SEC`S
 310-16
  
 11)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 TO FOOTER STEEL AND COLD WATER ETC
 AS PER 250-50 AND ALSO ANY BLDG STEEL.
  
 12)NOTE: PLEASE VERIFY OCP SHOWN FOR
 COND UNITS/ A/C.
  
 MIN 125%.
 PLEASE ALSO SIZE WIRE PER 310-16 (75~)
  
 13)NOTE: PLEASE SEE LOADING OF TRACK
 LIGHTING CIRCUIT.
  
 14)NOTE: PLEASE SHOW ALL CONTINUOUS AND
 MOTOR LOADS @125%. (EXT LTS).(ELEV)
 215-3/230-42
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS INTO TWO COMPLETE SETS
 FOR REVIEWING AND STAMPING.(MUST BE DONE
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717