2003-05-13 00:00:00 | ************* UNSAT ****************** |
| |
| 1)NOTE: PLEASE INCLUDE LICENSE # IN |
| TITLE BLOCK FOR ARCH OF RECORD AS REQ`D |
| IN FS/ FAC 61G1-16.004/ 481 |
| |
| 2)NOTE: PLEASE PROVIDE ROOM DESIGNATION |
| ON ALL SHEETS. PERMIT APPLICATION |
| MENTIONS A SHOWROOM? |
| |
| 3)NOTE: PLEASE CLARIFY HEIGHTS OF GFI`S |
| IN GARAGE. |
| |
| 4)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| PLANS AND CORRELATE W/ SUBMITTE PANEL |
| SCHEDULES. PLEASE CIRCUIT ALL EM/ EXT LT |
| -S PER 700-16E |
| |
| |
| 5)NOTE: PLEASE SHOW CONTROL AND CIRCUIT- |
| ING OF OUTSIDE LIGHTING. |
| |
| 6)NOTE: PLEASE SEE PLANS, THERE SEEMS |
| TO BE CIRCUITING SHOWN IN AREAS THAT DO |
| NOT GO TO ANYTHING? |
| |
| 7)NOTE: PLEASE COMPLETE LOAD CALCULATION |
| -S. SHOWN BLANK? |
| |
| 8)NOTE: PLEASE SHOW MISSING EQUIPMENT |
| GROUNDING CONDUCTORS FROM MAIN DISC`S TO |
| PANELS. 250-110/250-122 |
| |
| 9)NOTE: PLEASE CLARIFY SIZE ALLOWED FOR |
| FUTURE TENANT/METER AND MAIN DISC? |
| PLEASE BE SURE TO SIZE SEC`S FOR FUTURE |
| LOADS ALSO. SERVICE IS 400A`S AT PRESENT |
| TIME. |
| |
| 10)NOTE: PLEASE SIZE GROUNDING ELECTRODE |
| CONDUCTOR PER 250-66. BASED ON SEC`S |
| 310-16 |
| |
| 11)NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| TO FOOTER STEEL AND COLD WATER ETC |
| AS PER 250-50 AND ALSO ANY BLDG STEEL. |
| |
| 12)NOTE: PLEASE VERIFY OCP SHOWN FOR |
| COND UNITS/ A/C. |
| |
| MIN 125%. |
| PLEASE ALSO SIZE WIRE PER 310-16 (75~) |
| |
| 13)NOTE: PLEASE SEE LOADING OF TRACK |
| LIGHTING CIRCUIT. |
| |
| 14)NOTE: PLEASE SHOW ALL CONTINUOUS AND |
| MOTOR LOADS @125%. (EXT LTS).(ELEV) |
| 215-3/230-42 |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| INSERT NEW SHEETS INTO TWO COMPLETE SETS |
| FOR REVIEWING AND STAMPING.(MUST BE DONE |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |