2003-06-09 00:00:00 | PLEASE PROVIDE A COPY OF THE PAID |
| IMPACT FEE RECEIPT FROM PALM BEACH |
| COUNTY. |
| |
| THE BUILDING WILL BE LOCATED IN AN A8 |
| FLOOD ZONE WITH AN 15.0' BASE FLOOD |
| ELEVATION RELATIVE TO NGVD. |
| |
| THE BUILDING WILL BE A TWO STORY MIXED |
| OCCUPANCY OF B/M/S. |
| |
| PLEASE SHOW A LAYOUT OF THE PROPOSED |
| RACK STORAGE CALLED OUT ON SHEET A1.0 |
| SO THA EGRESS REQUIREMENTS MAY BE |
| DETERMINED. ALSO, INDICATE THE |
| QUANTITIES AND NATURE OF THE |
| COMMODITIES TO BE STORED.SEE FBC |
| 104.2. |
| |
| WHAT WILL THE ROOM SHOWN AS |
| "CONSTRUCTION" BE USED FOR?WHERE IS |
| THE EXIT DOOR? |
| |
| IS THE AREA SHOWN AS "CONCRETE LID" ON |
| SHEET A2.0 INTENDED FOR STORAGE OR |
| ANOTHER OCCUPANCY/USE?IF SO INDICATE |
| THE MINIMUM DESIGN LOADS AND |
| ACCESS/EGRESS. |
| |
| PLEASE PROVIDE DETAILS FOR THE STAIRS |
| INCLUDING RISE, RUN, HANDRAILS, FIRE |
| RATED ENCLOSURE PROTECTION,DESIGN |
| LOADS AND CONNECTION DETAILS. |
| |
| SHEET S1.1.SHOW THE DIMENSIONS FOR |
| THESECOND FLOOR BALCONY AND THE GUARD |
| RAIL DETAILS. |
| |
| SHOW HOW HURRICANE MISSILE IMPACT |
| RESISTANCE WILL BE ACCOMPLISHED FOR THE |
| EXTERIOR GAZED PORTIONS OF THE |
| BUILDINGS.SEEFBC 1606.1.4. |
| |
| PROVIDE THE STRUCTURAL INFORMATION ON |
| THE PLANS CALLED FOR IN FBC 1606.1.7. |
| |
| PLEASE PROVIDE THE ROOF COVERING DETAILS |
| IN ACCORDANCE WITH FBC 104.2.1.1. |
| |
| SHOW THE END BEARING DETAIL AND |
| CONNECTION FOR THE BAR JOISTS. |
| |
| SHEET S1.1.HOW IS THE TS COLUMN |
| ATTACHED TO THE WF BEAM? |
| |
| SHOW THE DESIGN SPECIFICATIONS FOR THE |
| PRECAST CONCRETE AND THE CONNECTION |
| BEARING DETAILS. |
| |
| SHOW A REINFORCEMENT DETAIL FOR THE |
| CANTILEVERED 6" SLAB AND THE BALCONY. |
| |
| SHOW THE FIRE RATED DOORS FOR THE STAIR |
| SHAFTS.SEE FBC TABLE 705.1.2. |
| |
| SHOW THE FIRE DESIGN NUMBER(S) FOR THE |
| STAIR AND ELEVATOR SHAFTS. |
| |
| SHOW THE FIRE SEPARATION, AND FIRE |
| DESIGN NUMBER FOR THE MIXED OCCUPANCY |
| SEPARATION.SEE FBC 704.1.1. |
| |
| SHOW THE INSTALLATION INFORMATION FOR |
| THE GLASS BLOCK.SEE FBC 2112.5. |
| |
| PLEASE PROVIDE SPECIFIC DESIGN |
| INFORMATION FOR THE "UNISTRUT WITH 5/8 |
| GYP BOARD" SHOWN ON SHEET A2.0. |
| |
| S1.1 AND S1.2.HOW IS THE TOP OF THE |
| PARAPET WALL FINISHED?LATERAL |
| REINFORCEMENT? |