Plan Review Notes
Plan Review Notes For Permit 03050237
Permit Number 03050237
Review Stop P
Sequence Number 2
Notes
Date Text
2003-07-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 CITY WPB CODE
  
 1) SECTION 90-123(D) WHERE SEWERS ARE
 AVAILABLE IT IS REQUIRED TO CONNECT TO
 SANITARY SEWER. THE CITY COMMISION IS
 AUTHORIZED TO GRANT VARIANCES TO THIS
 REQUIREMENT. (SEE ATTACHED SHEET)
 2) GRAB BARS NOT LOCATED IN STALLS SHALL
 COMPLY WITH 11-4.26 AND FIGURE #29. THE
 GRAB BAR BEHIND THE WATER CLOSET SHALL
 BE 36" MINIMUM. 42" MINIMUM FOR SIDE
 GRAB BAR. SHEET 301
 3) SHT 301 DETAIL #3, HEIGHT FOR SINK
 SHALL BE 34" PER 11-4.24.2. SHOW ON DE-
 TAIL.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]