2003-06-06 00:00:00DENIED:
  
 1.THE "TRACE LOAD 700" CALCS DO NOT
 MATCH THE ENERGY CALCS OR THE EQUIPMENT
 SCHEDULE.PLEASE REVISE.
  
 2.RETURN OR TRANSFER AIR REQUIRED FROM
 THE DEN AREA.
  