Plan Review Notes
Plan Review Notes For Permit 03050237
Permit Number 03050237
Review Stop E
Sequence Number 1
Notes
Date Text
2003-05-12 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE SHOW LOAD CALCULATIONS
 FOR COMMERCIAL USE. 220-3,220-11,220-11,
 220-13 ETC AND ALL CONTINUOUS LOADS AT
 125%. 215-3/230-42
  
 PLEASE SEE FIRE PLAN REVIEW, FOR ANY
 COMMENTS THAT MAY AFFECT ELECTRICAL
 PLANS. IE, EM LT AND EX LTS? 700-12E
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 PLEASE TAKE OUT OLD/VOIDED SHEETS AND
 INSERT NEW.
  