2003-06-18 00:00:00 | PLEASE PROVIDE A SURVEY/SITE PLAN | | LOCATING THE PROPOSED BUILDING ON THE | | PROPERTY. | | | | BEFORE A PERMIT TO CONSTRUCT MAY BE | | ISSUED IMPACT FEES MUST BE PAID TO THE | | COUNTY, THE PERMIT PLANS STAMPED BY | | THAT OFFICE AND A COPY OF THE PAID | | RECEIPT ATTACHED TO THE PERMIT | | APPLICATION.CALL 561-233-5025 FOR | | MORE INFORMATION. | | | | PROVIDE A CONSTRUCTION DETAIL FOR THE | | ATTACHMENT OF THE WINDOWS AND DOORS TO | | THE BUILDING.FBC 104.2. | | | | SPECIFY THE TYPE OF INSULATION IN THE | | WALLS AND CEILING.FBC 13-400. | | | | NOTE THE EMERGENCY ESCAPE WINDOW IN THE | | SLEEPING ROOM.FBC 1005.4. | | | | THE SPECIFICATIONS SECTION 03100-2 OMITS | | FOOTING FORMS.FORMS ARE REQUIRED BY | | CITY AMENDMENT TO FBC 1804.1.1.PLEASE | | REVISE AS NECESSARY. | | | | SECTION 08163-2 OF THE SPECIFICATIONS | | CITES SSTD 12-97, THE FBC INVOKES SSTD | | 12-99. | | | | THE LANDING AT THE ENTRANCE IS REQUIRED | | TO BE LEVEL FOR HC ACCESSIBILITY AND | | EGRESS REQUIREMENTS.SEE FBC 1012.1.3 | | AND 11-4.8.4. | | | | IT WOULD BE HELPFUL TO COLLATE THE | | PLANS TOGETHER AND PROVIDE A BINDING | | FOR THE SPECIFICATIONS. |
|