Plan Review Notes For Permit 03050231 |
Permit Number |
03050231 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-06-06 00:00:00 | DENIED: | | PLEASE NOTE 1 SET OF PLANS MISSING M-1, | | E-001 & E-201. | | | | 1.PLEASE INDICATE WHAT TYPE OF | | MAINTENANCE WILL BE DONE. (REPAIR GARAGE | | FOR AUTOMOBILES, LAWN EQUIPMENT, ETC.) | | | | 2.WHAT WILL BE STORED IN THE STORAGE | | AREAS?(COMBUSTIBLES?) | | | | 3.LOAD CALCS INDICATE COOLING AIRFLOW | | OF 2,089 CFM WHEREAS PLAN INDICATES ONLY | | 1435 CFM, WILL THE EQUIPMENT HAVE THE | | CAPACITY TO PRODUCE 2,089 CFM.ENERGY | | CALCS INDIATE A 57,300 TOTAL BTU SYSTEM | | WHICH CONFLICT WITH WHAT IS REFLECTED ON | | THE M-1 PLAN.PLEASE CLARIFY. | | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|