Plan Review Notes For Permit 03050231 |
Permit Number |
03050231 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-05-12 00:00:00 | ************ UNSAT ************** | | | | 1)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS | | AT 125%. 215-3/230-42 ETC | | | | 2)NOTE: PLEASE SHOW/ INCLUDE BLDG FOOTER | | STEEL AND ANY COLD WATER AS PART OF THE | | GROUNDING AT DEATCHED BLDG. 250-31 AND | | 250-50 | | | | PLEASE ALSO SEE ANY FIRE REVIEW COMMENTS | | THAT MAY AFFECT ELECTRICAL PLANS. | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|