Plan Review Notes For Permit 03050107 |
Permit Number |
03050107 |
|
Review Stop |
P |
Sequence Number |
8 |
|
Notes |
Date |
Text |
2004-12-13 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | | | 1) SHT P1.02 SANITARY LINE FROM HUB | | DRAINS FOR FIRE LINE DRAINS SHOWS | | DIRECTION OF FLOW IN TWO DIRECTIONS NEAR | | THE AIR INTAKE WELL. PLEASE CLARIFY. | | SECTION 104.2.1 | | 2) SHT P3.09 ACCUMULATED SQUARE FOOTAGE | | IN THE STORM SYSTEM IS NOT CORRECT. SEE | | AREA BY REVISION #3, 12" (20205) PLUS | | FORCED MAIN FROM BELOW (6900) SHOULD BE | | TOTAL OF 27105 SQ.FT., BUT PLANS SHOW | | 39385 SQ.FT. SECTION 104.2.1 | | 3) SHT P3.09 PIPING AT RISER "C" SHOWS | | 10" PIPE (9650), AND 8" (7960). 8" | | SHOULD READ (5380) AND 10" SHOULD READ | | (12980). SECTION 104.2.1. | | 4) SHT P3.10 FROM PREVIOUS COMMENT, | | PLEASE CORRECT THE SQ.FT. FROM RISER "C" | | TO READ 12,980 SQ.FT. AND 22,440 | | UPSTREAM OF THE STORM DRAIN LIFT | | STATION. SECTOPM 104.2.1. | | | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|