Date Text
2004-12-13 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT P1.02 SANITARY LINE FROM HUB
 DRAINS FOR FIRE LINE DRAINS SHOWS
 DIRECTION OF FLOW IN TWO DIRECTIONS NEAR
 THE AIR INTAKE WELL. PLEASE CLARIFY.
 SECTION 104.2.1
 2) SHT P3.09 ACCUMULATED SQUARE FOOTAGE
 IN THE STORM SYSTEM IS NOT CORRECT. SEE
 AREA BY REVISION #3, 12" (20205) PLUS
 FORCED MAIN FROM BELOW (6900) SHOULD BE
 TOTAL OF 27105 SQ.FT., BUT PLANS SHOW
 39385 SQ.FT. SECTION 104.2.1
 3) SHT P3.09 PIPING AT RISER "C" SHOWS
 10" PIPE (9650), AND 8" (7960). 8"
 SHOULD READ (5380) AND 10" SHOULD READ
 (12980). SECTION 104.2.1.
 4) SHT P3.10 FROM PREVIOUS COMMENT,
 PLEASE CORRECT THE SQ.FT. FROM RISER "C"
 TO READ 12,980 SQ.FT. AND 22,440
 UPSTREAM OF THE STORM DRAIN LIFT
 STATION. SECTOPM 104.2.1.
  
  