Plan Review Notes
Plan Review Notes For Permit 03050107
Permit Number 03050107
Review Stop E
Sequence Number 8
Notes
Date Text
2005-08-09 00:00:00********* UNSAT *********
  
 REV'S FOR SHEETS E 2.01,2.03,2.04
  
 1)NOTE: PLEASE SEE SOME UNITS, SD'S
 SHALL BE INSTALLED WITHIN 3' OF THE PEAK
 OF A CEILING. PLEASE SEE AREAS IN UNITS
 WHERE SD'S ARE SHOWN ON "LOWERED"
 CEILING AREAS.
 NFPA-72 8-1.4
  
 2)NOTE: PLEASE SEE LT FIXTURES SHOWN
 ABOVE MASTER BATH/ BATH TUBS DOES NOT
 INDICATE ANY CIRCUITING, CONTROL ETC.?
 215.5
  
 3)NOTE: PLEASE SEE 210.52C1 FOR KITCHEN
 COUNTERSPACE MIN RECEPT SPACING.
 UNIT B-2,A-1 MOD, PLEASE SEE ANY OTHER.
 210.52C1-C5
  
 4)NOTE: PLEASE ADJUST "DINING/LIVING"
 RM/AREAS SHOWN ON MOST OF THE "A" UNITS.
 PLEASE SEE LIVING RM IS SHOWN WHERE
 DINING RM CIRCUITS ARE SHOWN AND DINING
 RM WHERE LIVING RM IS SHOWN.
 215.5
  
 ***PLEASE SEE THAT WHEN PLANS ARE
 SUBMITTED, PLEASE SUBMIT THREE COMPLETE
 SETS WITH ALL SHEETS INSERTED INTO SETS
 IN ORDER. A AND E SHEETS WERE PLACED IN
 ORDER AND INTO THREE SETS BY THIS OFFICE
 ON THIS SUBMITTAL. PLEASE BE SURE ALL
 FUTURE PLANS ARE DONE IN ORDER TO
 EXPEDITE THE PLAN REVIEW PROCESS AND
 AVOID ANY POSSIBLE DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REIVEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]