2004-12-02 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT P1.01 COL. LINE P.4/P.B INDICATES
 THE PIPING TO (14) IS DELETED, BUT THE
 RISER IS STILL SHOWN. PLEASE CLARIFY.
 SECTION 104.2.1.
 2) STORM DRAIN LINE #9 BY ELEVATOR #1 BY
 COL. LINE P.4. PLEASE INDICATE WHERE
 THIS BRANCH LINE TIES INTO THE STACK.
 SECTION 104.2.1.
 3) REVISIONS ON THE SANITARY SYSTEM
 SHOWN ON SHT P1.01 SHALL BE REFLECTED ON
 THE SANITARY RISER DIAGRAM. PLEASE
 CORRELATE THE RISER DIAGRAM WITH THE
 FLOOR PLAN. SECTION 104.2.1.
 4) SHT P1.01 SANITARY LINE BY THE
 CLEANOUT NEAR COL.LINE P.5. PLEASE
 INDICATE WHERE THIS LINE TIES INTO.
 SECTION 104.2.1.
 5) SHT P3.10 THE STORM RISER DIAGRAM
 DOES NOT REFLECT THE LAYOUT ON SHEET
 P1.01. THE 3" PAD IS SHOWN CONNECTING
 BETWEEN THE TRENCH DRAINS ON THE LAYOUT
 SHEET, BUT DOWN STREAM OF BOTH TRENCH
 DRAINS ON THE STORMDRAIN ISOMETRIC.
 PLEASE CORRELATE THE RISER WITH THE
 LAYOUT. SECTION 104.2.1
  
  
  