Plan Review Notes
Plan Review Notes For Permit 03050107
Permit Number 03050107
Review Stop M
Sequence Number 7
Notes
Date Text
2005-06-04 00:00:001 PAGE M1.01 CAN NOT TAKE AIR FRON
 GARAGE TO PRESSUREISE STAIR TOWERS.
 2 PLEASE PROVIDE DOOR SCHEDULE PAGE A-48
 MISSING FROM PLANS.PLEASE PROVIDE TYPE
 OF DOOR USED FOR A/C CLOSITS IN SUITES.
 3 PLEASE SHOWDETAIL ON PLANS FOR
 RETURN AIR IN THE SUITES,FROM RETURN AIR
 GRILL TO A/C. UNITS.
 4 PAGE M2.05 STUDIO 1 SHOWES BOOSTER FAN
 IN DRYER EXHAUEST.REFER TO SECTION 504.6
 DOMESTIC CLOTHES DRYER DUCT,BOOSTER FANS
 ARE NOT AN EXCEPTION.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732