Plan Review Notes For Permit 03050107 |
Permit Number |
03050107 |
|
Review Stop |
M |
Sequence Number |
7 |
|
Notes |
Date |
Text |
2005-06-04 00:00:00 | 1 PAGE M1.01 CAN NOT TAKE AIR FRON | | GARAGE TO PRESSUREISE STAIR TOWERS. | | 2 PLEASE PROVIDE DOOR SCHEDULE PAGE A-48 | | MISSING FROM PLANS.PLEASE PROVIDE TYPE | | OF DOOR USED FOR A/C CLOSITS IN SUITES. | | 3 PLEASE SHOWDETAIL ON PLANS FOR | | RETURN AIR IN THE SUITES,FROM RETURN AIR | | GRILL TO A/C. UNITS. | | 4 PAGE M2.05 STUDIO 1 SHOWES BOOSTER FAN | | IN DRYER EXHAUEST.REFER TO SECTION 504.6 | | DOMESTIC CLOTHES DRYER DUCT,BOOSTER FANS | | ARE NOT AN EXCEPTION. | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|