Plan Review Notes
Plan Review Notes For Permit 03050107
Permit Number 03050107
Review Stop E
Sequence Number 6
Notes
Date Text
2005-07-12 00:00:00******** UNSAT *********
  
 1)NOTE: PLEASE SEE MIN ALTERNATING
 CIRCUITS REQUIRED IN EGRESS HALLWAYS, OR
 AN ALTERNATE METHOD TO INSTALL A BATTERY
 BACK UP FIXTURE IN ALTERNATING
 LOCATIONS.
 PLEASE SEE LS 101 7-9, ALTERNATING THE
 HALLS EGRESS CIRCUITS WILL HELP
 ALLEAVIATE LEAVING ANY ONE AREA IN TOTAL
 DARKNESS UPON THE TRIPPING OF ONE
 BREAKER ETC.
 PLEASE ALSO SEE SPEACIAL USEAGE RMS,
 ELEC, FIRE PUMP, FIRE COMMAND RM ETC.
 GEN RM ALREADY SHOWS BATT BACK UP
 FIXTURES ON EM CIRCUIT.
 PLEASE SEE STAIR TOWERS ARE ALREADY
 SHOWN WITH ALTERNATING EM CIRCUITS.
 700.16 ALSO.
  
 2)NOTE: PLEASE PROVIDE ROOM DESIGNATIONS
 ON ROOF TOP PLANS.
 PLEASE SEE THE FOLLOWING COMMENT.
  
 3)NOTE: PLEASE SEE 620.23,620.24 FOR
 REQUIRED DEDICATED BRANCH CIRCUITS FOR
 EACH OF THE ELEVATOR MACHINE ROOMS.
 THESE CIRCUITS MAY NOT BE SHARED WITH
 OTHER AREAS AS SHOWN.
  
 4)NOTE: PLEASE SEE680.22B, NO LIGHTING
 FIXTURES ARE PERMITTED WITHIN THE 5'
 EXTENDING OUTWARD FROM POOL'S WATER
 EDGE.
 PLEASE SEE LANSCAPE LIGHTING FIXTURES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  