2004-06-25 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 NOTE:
 THREE COPIES OF ACHITECTURAL SHEETS
 A.02, A.03, A.35 AND LS.5 WERE AMENDED,
 SIGNED AND DATED BY GUILLERMO ENCINOSA
 (ARCHITECT OF RECORD) HY HAND ON 6/23/04
  
 --PROVISO--
 SUBMIT METAL LOUVERED DOOR PRODUCT
 APPROVALS FOR DOORS WITH DESIGN PRESSURE
 RATINGS OF AT LEAST +70 PSF AND -80 PSF.
 SHEET A.48, DOOR SCHEDULE, SHOWS
 LOUVERED DOORS (TYPE H AND G) FOR DOORS
 43, 93 AND 94 (TO THE GENERATOR, BOILER
 AND PUMP ROOMS).THE SUBMITTED CURRIES
 COMPANY PRODUCT APPROVAL NOA# 03-0319.04
 HAS A MAXIMUM DESIGN PRESSURE RATING OF
 ONLY +50 PSF AND -50 PSF.