Plan Review Notes For Permit 03050107 |
Permit Number |
03050107 |
|
Review Stop |
B |
Sequence Number |
6 |
|
Notes |
Date |
Text |
2004-06-25 00:00:00 | BUILDING PLAN REVIEW | | ******PROVISO******* | | ROBERT BROWN(561) 805 6716 | | E-MAIL: [email protected] | | | | NOTE: | | THREE COPIES OF ACHITECTURAL SHEETS | | A.02, A.03, A.35 AND LS.5 WERE AMENDED, | | SIGNED AND DATED BY GUILLERMO ENCINOSA | | (ARCHITECT OF RECORD) HY HAND ON 6/23/04 | | | | --PROVISO-- | | SUBMIT METAL LOUVERED DOOR PRODUCT | | APPROVALS FOR DOORS WITH DESIGN PRESSURE | | RATINGS OF AT LEAST +70 PSF AND -80 PSF. | | SHEET A.48, DOOR SCHEDULE, SHOWS | | LOUVERED DOORS (TYPE H AND G) FOR DOORS | | 43, 93 AND 94 (TO THE GENERATOR, BOILER | | AND PUMP ROOMS).THE SUBMITTED CURRIES | | COMPANY PRODUCT APPROVAL NOA# 03-0319.04 | | HAS A MAXIMUM DESIGN PRESSURE RATING OF | | ONLY +50 PSF AND -50 PSF. |
|