Plan Review Notes
Plan Review Notes For Permit 03050107
Permit Number 03050107
Review Stop P
Sequence Number 5
Notes
Date Text
2004-06-17 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) FROM PREVIOUS REVIEW: SHTS A.51 THRU
 A.66 CALCULATIONS FOR 20GA METAL BACKING
 ALL SHEETS SHALL BE SIGNED, SEALED AND
 DATED. ALL INFORMATION FOR TITLE BLOCK
 IS REQUIRED ON ALL SHEETS. ONLY ONE SET
 HAS SEAL/SIGNATURE/DATE OTHER SETS ARE
 COPIES. FAC 61G15-23.002(1)(2) - FS 471.
 025 - ALSO ABOVE MENTIONED SHEETS
 STILL SHOW 20 GA METAL BACKING WHILE THE
 CALCULATIONS INDICATE 16GA METAL BACKING
 CORRELATE PLANS WITH CALCULATIONS. ALSO
 SEE DETAILS ON SHT A.67. SEC 104.2.1
 2) SHT A.63 CLEAR FLOOR SPACE FOR LAV IS
 NOT SHOWN. ALSO LAV SHALL BE CENTERED ON
 THE 48" SIDE OF THE 30"X48" CLEAR FLOOR
 SPACE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]