Plan Review Notes For Permit 03050107 |
Permit Number |
03050107 |
|
Review Stop |
M |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2004-06-24 00:00:00 | JACK NEDLIN, ENGINEER (STEVEN FELLER, | | INC) CORRECTED PLAN SHEETS M1.01, M1.02 | | AND REPLACED IN SUBMITTED SET.PLAN | | SHEETS M1.03 & M1.04, ENGINEER MADE | | NOTES & SIGNED.M1.03, DUCT AT CEILING | | OF STAIRWELL - THIS WILL HAVE A MINIMUM | | OF 1 HR LID AND WILL NOT IMPEDE THE | | STAIRWELL.PLAN SHEET M1.04, CHANGED | | NOTE INDICATING PROPER WG. (MIN 0.05" | | WG TO 0.35 " WG MAX).CHANGED SEQUENCE | | FOR THE DAMPERS ON SMOKE CONTROL. |
|