Plan Review Notes
Plan Review Notes For Permit 03050107
Permit Number 03050107
Review Stop M
Sequence Number 5
Notes
Date Text
2004-06-24 00:00:00JACK NEDLIN, ENGINEER (STEVEN FELLER,
 INC) CORRECTED PLAN SHEETS M1.01, M1.02
 AND REPLACED IN SUBMITTED SET.PLAN
 SHEETS M1.03 & M1.04, ENGINEER MADE
 NOTES & SIGNED.M1.03, DUCT AT CEILING
 OF STAIRWELL - THIS WILL HAVE A MINIMUM
 OF 1 HR LID AND WILL NOT IMPEDE THE
 STAIRWELL.PLAN SHEET M1.04, CHANGED
 NOTE INDICATING PROPER WG. (MIN 0.05"
 WG TO 0.35 " WG MAX).CHANGED SEQUENCE
 FOR THE DAMPERS ON SMOKE CONTROL.