Plan Review Notes
Plan Review Notes For Permit 03050107
Permit Number 03050107
Review Stop FIRE
Sequence Number 5
Notes
Date Text
2004-06-16 00:00:001) ELECTRONIC SWITCHES, CHAIN AND LOCK
 REQUIRED ON FIRE LINE BACKFLOW DEVICE.
  
 2) TACTILE SIGNAGE REQUIRED AT ALL
 EXITS.
  
 3) PLEASE LABEL ALL STRETCHER ACCESSIBLE
 ELEVATORS WITH SIGNAGE.
  
 4) EXIT SIGN NEEDED ADJACENT TO
 BUSINESS CENTER TO DIRECT PERSONS TO
 EXIT SIGN NEAR MAIL ROOM.
  
 5) VERIFY DOOR SWINGS. DOUBLE DOORS NEAR
 ASST. MANAGER OFFICE SWINGING IN THE
 RIGHT DIRECTION. CORRIDOR 027 SWINGS
 IN.
  
 6) NO ELECTRIC OR EQUIPMENT ALLOWED WITH
 STAIRWELLS EXCEPT THAT IS ALLOWED UNDER
 NFPA 101, LIFE SAFETY CODE, 2000 EDITION
 CHAPTER SEVEN.
  
 7) ALL SMOKE DETECTORS SHALL BE A
 MINIMUM OF THREE FEET OF AC DIFFUSERS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910