Plan Review Notes
Plan Review Notes For Permit 03050107
Permit Number 03050107
Review Stop B
Sequence Number 5
Notes
Date Text
2004-06-23 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 NOTE:
 THREE COPIES OF ARCHITECTURAL SHEETS
 A.02, A.03, A.35AND LS.5 WERE AMENDED,
 SIGNED AND DATED BY GUILLERMO ENCINOSA
 (ARCHITECT OF RECORD) BY HAND ON 6/23/04
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 4/16/04:
  
 1) THE COMMENT RESPONSE, DATED 5/8/04,
 IS NOTED.
 THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2) THE COMMENT RESPONSE, DATED 5/8/04,
 IS NOTED.
 IMPACT FEES. THE PLANS SHALL BE TAKEN
 TO PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE A PERMIT CAN BE ISSUED.
  
 4) DECLARATION OF CONDOMINIUM BEFORE
 C.O. ISSUE.THE COMMENT RESPONSE, DATED
 5/8/04 IS NOTED.
  
 6) FBC* 105.13.1SPECIAL INSPECTOR.
 THIS COMMENT HAS NOT BEEN ADDRESSED. THE
 'SPECIAL INSPECTOR AGREEMENT' WAS NOT
 RE-SUBMITTED.REPEATING THE COMMENTS
 FROM THE PREVIOUS REVIEW, THE SUBMITTED
 'SPECIAL INSPECTOR AGREEMENT' IS MISSING
 THE LAST PAGE, WHICH IS TO BE SIGNED BY
 THE CONTRACTOR AND ARCHITECT/ENGINEER
 THE AGREEMENT SHALL ALSO BE SIGNEED BY T
 HE OWNER AND JOB INSPECTOR IN THE SPACE
 ALLOCATED.ALL SIGNATURES ARE TO BE
 NOTARIZED ORIGINALS.
  
 7) SEPARATE SWIMMING POOL PERMIT APPLIC.
 THE COMMENT RESPONSE, DATED 5/8/04, IS
 NOTED.
  
 9) FBC 13-103.1.2ENERGY CODE
 COMPLIANCE FORMS.THE COMMENT RESPONSE
 DATED 5/8/04, IS NOTED BUT SHEET 2 OF
 THE SUBMITTED ENERGY CODE COMPLIANCE
 FORMS SHALL BE SIGNED BY A KENCO
 COMMUNITIES REPRESENTATIVE AS 'OWNER',
 TO CERTIFY COMPLIANCE.
  
 11) PRODUCT APPROVALS.THIS COMMENT HAS
 NOT BEEN PROPERLY ADDRESSED.
 NO PRODUCT APPROVALS HAVE BEEN SUBMITTED
 FOR THE ROOFING PRODUCTS, STOREFRONT AND
 HOLLOW METAL, LOUVERED, FLUSH (SINGLE
 AND DOUBLE AND ALUMINUM GLAZED SWING
 (SINGLE AND DOUBLE) EXTERIOR DOORS.
  
 50) SHEET A.29PRE-CAST CONCRETE
 ARCHITECTURAL FEATURES/MOLDINGS.ONE
 OF THE THREE SETS OF PLANS STILL HAS
 THE 'OLD' REVISION OF SHEET A.29. INSERT
 THE LATEST REVISION AND REMOVE THE 'OLD'
 SHEET.
  
 52) FBC 412.5(3)SHEET M4.01, SMOKE
 CONTROL NOTE C.THIS COMMENT HAS NOT
 BEEN PROPERLY ADDRESSED.THE REVISION
 MADE IS NOTED BUT THE NOTE C STILL DOES
 NOT MAKE SENSE AND DOES NOT CLEARLY
 EXPRESS THE ENGINEER'S INTENT.PLEASE
 READ THE NOTE AND CONSIDER THAT IT MAY
 BE CLARIFIED BY:
 - DELETING THE WORDS "..THROUGH THE..."
 FROM THE SECOND SENTENCE.
 - REPLACING THE WORDS "TO CLOSE AND..."
 WITH "IT SHALL ALSO..." AT THE BEGINNING
 OF THE LAST SENTENCE.
  
 53) FBC 1005.6.9.9SHEET M4.01, SMOKE
 CONTROL NOTE 3B - STAIR BAROMETRIC
 RELIEF.THIS COMMENT HAS NOT BEEN
 PROPERLY ADDRESSED. THE REVISION MADE IS
 NOTED BUT THE NOTE SPECIFIES A MINIMUM
 PRESSURE DIFFERENCE OF 0.35"WG WHILE
 FBC 1005.6.9.9 REQUIRES A PRESSURE
 DIFFERENCE OF 0.05"WG MINIMUM AND
 0.35"WG MAXIMUM.AMEND THE NOTE TO
 DEMONSTRATE COMPLIANCE.
  
 54) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
 PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS