Plan Review Notes
Plan Review Notes For Permit 03050107
Permit Number 03050107
Review Stop P
Sequence Number 4
Notes
Date Text
2004-04-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
 FHA-AMEND. 98 DESIGN MANUAL
  
 A) COMMENTS FROM FIRST TWO REVIEWS NOT
 ADDRESSED SUFFICIENTLY.
 1) SHTS A.11 & A.12 ALL PUBLIC & COMMON
 USE TOILET ROOMS SHALL COMPLY WITH SEC.
 11-4.22 AND ALL SUBSECTIONS. CLEAR FLOOR
 SPACE IS NOT SHOWN FOR WATER CLOSET AND
 LAV IN ACCESSIBLE STALLS IN MENS AND
 WOMENS TOILET ROOMS. (019)
 2) PLEASE SUBMIT CALCULATIONS FOR MINI-
 MUM FIXTURE FACILITIES PER TABLE 403.1.
 MORE INFORMATION REQUIRED. INDICATE ROOM
 NUMBER, ROOM USAGE, AND SQUARE FEET FOR
 EACH ROOM. (EXAMPLE - MAIL ROOM - MGR
 ROOM ECT)
 3) INDICATE LOCATION OF SCUPPER DETAIL
 THAT SHOWS HEIGHT AND WIDTH. DETAIL ON
 SHEET A.45 DOES NOT SHOW HEIGHT OR THE
 WIDTH.
 4) SHTS A.51 THRU A.66 UNIT NOTES #7,
 CALCULATIONS FOR 20GA METAL BACKING.
 RESPONSE "SEE CHM CALCULATIONS" WHERE
 ARE THE CHM CALCULATIONS LOCATED? ALSO
 WHAT ARE CHM CALCULATIONS? IS THERE A
 SHEET WITH THE ABBREVIATIONS SHOWN?
 5) SHT A.11 BAR SINK SHALL COMPLY WITH
 11-4.24 AND ALL SUBSECTIONS. PROVIDE A
 DETAIL. - RESPONSE STATES SHOWN ON SHEET
 A.68 - A.68 SHOWS OUTSIDE ELEVATIONS.
 NO BAR SINK ELEVATIONS SHOWN. (3B)
 6) SCUPPER DETAIL DOES NOT SHOW HEIGHT
 OR WIDTH. THIS INFORMATION IS REQUIRED
 TO DETERMINE THE SIZE OF THE SCUPPER.
 (4B)
 7) SHTS A.51 THRU A.66 SHOW CLEAR FLOOR
 SPACE FOR ALL ACCESSIBLE FIXTURES PER
 FHA DESIGN MANUAL PAGE 7.43 - ALL FIX-
 TURES OF ALL UNITS DO NOT SHOW CLEAR
 FLOOR SPACE.
 8) IT APPEARS THAT SOME OF THESE COMM-
 ENTS HAVE BEEN REJECTED AT LEAST 3 TIMES
 AND A 4 TIMES THE FEE MAY BE ACCESSED.
  
 REVIEW BY KEN STEVENS