2004-04-10 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 FUEL GAS |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| FBC-2001 BUILDING |
| FHA-AMEND. 98 DESIGN MANUAL |
| |
| A) COMMENTS FROM FIRST TWO REVIEWS NOT |
| ADDRESSED SUFFICIENTLY. |
| 1) SHTS A.11 & A.12 ALL PUBLIC & COMMON |
| USE TOILET ROOMS SHALL COMPLY WITH SEC. |
| 11-4.22 AND ALL SUBSECTIONS. CLEAR FLOOR |
| SPACE IS NOT SHOWN FOR WATER CLOSET AND |
| LAV IN ACCESSIBLE STALLS IN MENS AND |
| WOMENS TOILET ROOMS. (019) |
| 2) PLEASE SUBMIT CALCULATIONS FOR MINI- |
| MUM FIXTURE FACILITIES PER TABLE 403.1. |
| MORE INFORMATION REQUIRED. INDICATE ROOM |
| NUMBER, ROOM USAGE, AND SQUARE FEET FOR |
| EACH ROOM. (EXAMPLE - MAIL ROOM - MGR |
| ROOM ECT) |
| 3) INDICATE LOCATION OF SCUPPER DETAIL |
| THAT SHOWS HEIGHT AND WIDTH. DETAIL ON |
| SHEET A.45 DOES NOT SHOW HEIGHT OR THE |
| WIDTH. |
| 4) SHTS A.51 THRU A.66 UNIT NOTES #7, |
| CALCULATIONS FOR 20GA METAL BACKING. |
| RESPONSE "SEE CHM CALCULATIONS" WHERE |
| ARE THE CHM CALCULATIONS LOCATED? ALSO |
| WHAT ARE CHM CALCULATIONS? IS THERE A |
| SHEET WITH THE ABBREVIATIONS SHOWN? |
| 5) SHT A.11 BAR SINK SHALL COMPLY WITH |
| 11-4.24 AND ALL SUBSECTIONS. PROVIDE A |
| DETAIL. - RESPONSE STATES SHOWN ON SHEET |
| A.68 - A.68 SHOWS OUTSIDE ELEVATIONS. |
| NO BAR SINK ELEVATIONS SHOWN. (3B) |
| 6) SCUPPER DETAIL DOES NOT SHOW HEIGHT |
| OR WIDTH. THIS INFORMATION IS REQUIRED |
| TO DETERMINE THE SIZE OF THE SCUPPER. |
| (4B) |
| 7) SHTS A.51 THRU A.66 SHOW CLEAR FLOOR |
| SPACE FOR ALL ACCESSIBLE FIXTURES PER |
| FHA DESIGN MANUAL PAGE 7.43 - ALL FIX- |
| TURES OF ALL UNITS DO NOT SHOW CLEAR |
| FLOOR SPACE. |
| 8) IT APPEARS THAT SOME OF THESE COMM- |
| ENTS HAVE BEEN REJECTED AT LEAST 3 TIMES |
| AND A 4 TIMES THE FEE MAY BE ACCESSED. |
| |